beautypg.com

4 flue – Glow-worm EnergySaver 80 User Manual

Page 12

background image

12

221837B

Diagram 4.1

0158M(a)

2

˚

35mm

1metre

SIDE FLUE

FRONT VIEW

Make sure flue slopes
2

˚

down

towards the boiler
that is 35mm fall per metre
of flue length (2

˚

)

Make sure flue slopes
2

˚

down towards

the boiler
that is 35mm fall
per metre
of flue
length (2

˚

)

300mm

2

˚

10.5mm

REAR FLUE

SIDE VIEW

4 Flue

NOTE:

The flue must be installed in accordance with the current issue
of BS5440 Part 1.

Important. The flue must be installed with a fall of: 35mm per
metre (2

o

) TOWARDS the boiler, see diagram 4.1.

It is of no advantage to exceed the angle of 2

o

, indeed sealing

of the fan to the flue elbow may become more difficult as the
angle is increased.

The air and flue duct connect to the top of the boiler using an
elbow which can be positioned to the side or rear.

The rear and side flue assemblies are designed for internal
installation, but if necessary, due to insufficient clearances
(boiler/flue terminal location) they can be installed from the
outside.

For a wall thickness up to 300mm the flue can be fully installed
from the inside.

For a wall thickness over 300mm the external cut hole will need
to be made good from the outside.

The standard flue is able to provide the duct lengths as shown
in diagram 4.2 for a rear flue and diagram 4.3 for a side flue.

If a longer flue duct is required, do not extend the ductings. A
1, 2 or 3metre flue and terminal can be supplied.

See diagrams 4.2 and 4.3

S = "External wall face" to "boiler casing"

Diagram 4.3

REAR FLUE LENGTHS

SIDE FLUE LENGTHS

Diagram 4.2

R = Wall Thickness

STD Flue pack

80mm to 311mm

STD Flue pack

75mm to 442mm

3m Flue pack

75mm to 2933mm

2m Flue pack

75mm to 1953mm

3m Flue pack

80mm to 2801mm

2m Flue pack

80mm to 1821mm

1m Flue pack

75mm to 953mm

1m Flue pack

80mm to 821mm

'R'

'S'

6861

6860