13 Fault Finding

PUMP OVERRUN OPERATION

The control thermostat has a pump overrun facility built into it, when the control thermostat is

set at maximum only, the pump overrun will keep the pump running to allow the boiler to cool

down after which it will stop, providing the remote controls are NOT calling for heat.

FAULT FINDING

Turn boiler control thermostat to maximum, with the remote controls calling for heat, does the

pump continue to run after the appliance has shut down on boiler control thermostat ?

Turn off remote controls,

does pump stop after a short

period of time

Is there 240V~ on L ?

Is there 240V ~on

9 connection on thermostat ?

Faulty permanent

live feed.

Replace

Faulty pump overrun.

Replace control thermostat

Pump overrun in order

Is there 240V ~ on PL for pump ?

Faulty pump/wiring ? Replace or
repair as necessary

NO

YES

YES

YES

YES

YES

NO

NO

NO

NO

Faulty

connections

between

thermostat and

interconnection

PCB. Repair

Faulty

connections

between

thermostat and

interconnection

PCB. Repair