ENMET OMNI-4000 User Manual

Page 56

background image

ENMET Corporation

OMNI-4000 S/N 6705 and above

50

Setting the Zero
The display shows alternately:

• Press ENTER to display the zero value. The display shows, for example:

• Set the zero point using the zero potentiometer; see Figure 3-11. Turn the potentiometer clockwise to increase the

displayed value.

The display must show a value close to zero:

In case of problems with the setting, replace the
sensor.

• Press ENTER when the smallest possible value

has been obtained.

Setting the Sensitivity
Preparing the Equipment:

• Attach the calibration cover; see Figure 3-12.
• Connect the calibration gas cylinder to the

calibration cover using the vinyl hose.

Figure 3-11: Location of Explosive Gas

Channel Zero Potentiometer

Figure 3.12: Calibration Gas Equipment Arrangement

Please wait for

stabilization

Then set

zero

Zero

5%LEL

CH4

Zero

10.0%

CH4

Gas Cylinder

Regulator

Hose

Calibration
cover

Zero Potentiometer