Part vii. faq – Austin Hughes IPM-03 User Manual
Page 49
www.austin-hughes.com
UM-IPM-03-Q214V3
P.44
IP dongle
1. What is the IP dongle?
The IP dongle provides a simple and economical way to consolidate management of max. 16 pcs WSi
Outlet kWh Switched / Wi Outlet kWh Monitored / WS kWh Switched / W kWh Monitored PDUs, by a single
IP connection to the network.
2. What is the IP setup utilities?
This is a windows application used to assign the IP address of IP dongle. You can download the IP setup
utilities from the link below:
http://www.austin-hughes.com/support/utilities/infrapower/IPdongleSetup.msi
3. Does the IP dongle support DHCP (Dynamic Host Confi guration Protocol)?
No, the IP dongle only works with static IP-address.
4. Will the reset of IP dongle affect the power to the outlets?
No, the IP dongle operates on a separate circuit, so the power to the outlets will remain unchanged.
5. How can I replace a failed IP dongle?
As the IP dongle is hot swappable, without power disconnection, you can unplug the RJ45 connector and
slide out the failed IP dongle from the WSi Outlet kWh Switched / Wi Outlet kWh Monitored / WS kWh
Switched / W kWh Monitored PDU. Then replace a new one for the PDU and re-confi gure the IP address
to fi t your network setting. ( Please refer to user manual < 2.2 > for details )
Temp. Humidity sensor
1. How accurate is the Temp. & Humid. sensor?
It is accurate to ± 1°C ( typical ) & ± 4.5% RH ( typical ).
2. How accurate is the Temp. sensor?
It is accurate to ± 1.5°C ( typical ).
3. How to install the Temp. / Temp. & Humid. sensor ?
Plug in the Temp. / Temp. & Humid. sensor ONLY AFTER the PDU is ON.
10. Is it possible to manage the WSi Outlet kWh Switched / Wi Outlet kWh Monitored / WS kWh
Switched / W kWh Monitored PDUs from different workstations?
Yes, the InfraPower manager supports 5 concurrent login users from different workstations.