30

System

Management

Version Info

Displays the current firmware version and 10MHz clock source.

3.2.2

Threshold and Control

Provides operational and threshold settings for the PXES-2590,
including target temperature, fan mode, and threshold settings for
DC voltage, temperature, and cooling fan speeds.

Target Temperature

Fans run at different speeds based on the monitored tempera-
ture, when the Fan switch on the rear panel is set to AUTO.

Target Temp indicates the temperature when the fans are at

100%. Using the default 50°C as an example, fans run at 40%
when all temperature readings are less than 25°C, and begin
rampup when any reading exceeds 25°C. The fans run 100%
speed if any temperature reading exceeds 50°C (Target Tem-
perature). Target temperature setting parameters are as
shown.