Mcrion 10, Tools niidid ror installation, Tools needed for installation – Bard Bayrd Furnace 403293A User Manual
Page 19
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
![background image](/manuals/723602/19/background.png)
National Fuel Gas Code ANSI Z223.1/NFPA 54.
Rabuild a chimney to meet national standards.
WARNINOi
An Inadequate vent or chimney
could allow combuatlon products to collect
In structure, resulting In Injury or death.
d.
Sometimes you wiii repiace a common vented
appliance. Make sure common vent size is cor
rect for aJl appliances connected to it. If you re
move a furnace from a common vent without
replacing it, the vent will likely be too large for
remaining appliances. See Venting Addendum.
e.
The following steps shall be followed with each
appliance remaining connected to common vent
ing system placed in operation, while other ap
pliances remaining connected to common venting
system are not in operation.
1.
Seal any unused openings in common vent
ing system.
2.
Visually inspect venting system for proper
size and horizontal pitch and determine there
is no blockage or restriction, leakage, corro
sion and other deficiencies which could
cause an unsafe condition.
3.
Insofar as is practical, close all building doors
and windows and all doors between space
in which appliances remaining connected to
common venting systems are located and
other spaces of building. Turn on clothes
dryers and any appliances not connected to
common venting system. Turn on any ex
haust fans, such as range hoods and bath
room exhausts so they will operate at maxi
mum speed. Do not operate a summer ex
haust fan. Close fireplace dampers.
4.
Follow Operating Instructions. Place appli
ance being inspected in operation. Adjust
thermostat so appliance will operate con
tinuously.
5.
After it has been determined that each ap
pliance remaining connected to common
venting system properly vents when tested
as outlined above, return doors, windows,
exhaust fans, fireplace dampers and any
other gas-burning appliance to their previous
conditions of use.
6.
If improper venting is observed during any
of the above tests, common venting systems
must be corrected.
NOTE: Follow current National Fuel Gas
Code ANSI 2223.1/NFPA 54 to correct im
proper common vent operation. Any common
vent resizing must approach minimum size
determined by using Venting Addendum.
MCriON 10 —
TOOLS NIIDID rOR INSTALLATION.
ITEM
TOOL DESCRIPTION
USED FOR
A.
HAND TOOLS
1.
Carton KnHe
Furnace removal from
carton
2.
1/4" nut driver
Control box cover
3.
5/16" nut driver
Casing and blower
4.
3/8” nut driver
Blower and motor
mounts
5.
1/4" X 8" straight-
blade screwdriver
Wire terminals and manifold
pressure adjustment
6.
#2
X 8"
Phillips
screwdriver
Components in control box
7.
7/16" open end or
tubing wrench
Main burner orifices
8.
2-8" to 14" pipe
wrenches
Gas pipe installatbn
9.
4" adjustable
wrench
Blower wheel set screw
tightening
10.
8” Channel-lock
ptiei^
Strain reliefs
11.
3/16" Allen
wrench
Inlet and outlet pressure tap
plug removal from gas control
12.
9/64" Allen
wrench
Honeywell gas inlet fitting
B.
SUPPLIES
13.
Pipe thread sealant
suitable for use with
propane (LP) gas
Gas pipe and controls
14.
Bottle of soap
solutbn
Gas leak checking
15.
2-1/8” pipe, manual
shutoff valves
Gas control inlet and
pressure checking
C.
TEST INSTRUMENTS
16.
Volt meter with 50
and 150 volt ranges
Electrbal chedt of controls
and power supply
17.
Clamp around
ammeter with 10 amp
and higher ranges
Amp draw of motors and
control check
17