Bryant 396G User Manual
I nsta i lation i nstructions, Counterflow gas-fired forced-air furnace, Ipip í
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

i nsta I lation i nstructions
COUNTERFLOW GAS-FIRED
FORCED-AIR FURNACE
INTRODUCTION
Before installing the fiimace, refer to "Procedure for Gas-
Fired Furnaces” (packaged with the equipment) for informa
tion concerning combustion, venting, piping, and other stan
dard installation practices. Further reference is made to the
ciurrent edition of the American National Standard Z223.1
National Fuel Gas Code.
Each furnace is shipped from the factory completely assem
bled with multispeed direct-drive blower and wired ready for
counterflow indoor heating installation only. All sizes
feature a printed-circuit board control center with easy-to-
read, low-voltage terminal strip to ensure proper connec
tions.
The efficiency rating of the furnace is a product thermal
efficiency rating determined under continuous operating
conditions independent of any installed system.
CAUTION:
Do not install furnace in a corrosive or contami
nated atmosphere. Make sure all combustion and circulating
air requirements listed in "Procedure for Gas-Fired Fur
naces” are adhered to, in addition to, all local codes and
ordinances.
The design of the counterflow gas-fired furnace is A.G.A. cer
tified for installation on combustible flooring (with optional
floor base), in alcoves, basements, closets, or utility rooms.
This furnace line is
not
A.G.A. certified for installation in a
mobile home, recreation vehicle, or outdoors.
TABLE i-CLEARANCES (In Inches)
Sizes
050
075 thru 150
Sides—Single-Wall Vent
1
1
Type-B Double-Wall Vent
0
1
Back
0
0
Top of Plenum
1
1
Vent Connector—Single-Wall
6
6
Type-B Double-Wall
1
1
Front—Combustion Air
6
6
Service
30
30
Installation comprises the following:
I. Inspection
II. Location, Ventilation, and Air for Combustion
III. Gas Piping
IV. Venting
All of the above steps are covered in general by the like-num
bered sections of the "Procedure for Gas-Fired Furnaces”
booklet packaged with the furnace; therefore, these Installa
tion Instructions will contain only supplementary informa
tion applicable to installing the furnace.
In addition, the following sections deal specifically with in
stallation of the 396G:
V. Supply-Air Plenum Installation
VI. Electrical
VII. Sequence of Operation
VIII. Filter
IX. Startup and Adjustment
X. Care and Maintenance
For accessory installation details, refer to applicable in
stallation literature.
Cancels: 40396DP5-A
and 40396DP6-A
40396DP7-A
1/15/80
I ! '
I" r,
---- - !
.- i
Ipip Í
A78593
Figure 1—Model 396G036075 With Optional
Vent Damper Installed
V.
SUPPLY-AIR PLENUM INSTALLATION
A. Installation on a concrete slab
1. See Figure 2 for dimensions and location of supply-air
opening in furnace bottom.
2. Construct hole in floor per dimensions in Figure 3 eind
Table IV.
3. Place plenum and furnace as shown in Figure 4.
B. Installation on a combustible floor
1. Read Installation Instructions packaged with combusti
ble floor base.
2. Cut and frame hole in floor per dimensions in Table I of
Installation Instructions packaged with combustible floor
base. If this requires cutting of a floor joist, tie ends of cut
joist into adjacent joists so that proper floor support will be
maintained.
3. Assemble and install combustible floor base per instruc
tions packaged with base.
4. When completed, combustible floor base, plenum, and
furnace (or coil casing when used) should be installed as
shown in Figure 6.
RDP Company, Division of Carrier Corp.
Document Outline
- i nsta I lation i nstructions
- Figure 1—Model 396G036075 With Optional Vent Damper Installed
- TABLE ll-DIMENSIONS (in Inches)
- Figure 2—Dimensional Drawing
- TABLE lil-RATINGS AND PERFORMANCE*
- Figure 3 — Floor Opening for Concrete Siab
- TABLE IV —OPENING DIMENSIONS
- 050 thru 150 IID LPG
- tABlE V — PILOT GAS GONSUMPTlÓ^J
- TABLE VI-SPEED SELECTOR
- Penn Model J996 Figure 18 — Position of Electrode to Pilot