beautypg.com

Bryant 396G User Manual

I nsta i lation i nstructions, Counterflow gas-fired forced-air furnace, Ipip í

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

i nsta I lation i nstructions

COUNTERFLOW GAS-FIRED
FORCED-AIR FURNACE

INTRODUCTION

Before installing the fiimace, refer to "Procedure for Gas-
Fired Furnaces” (packaged with the equipment) for informa­

tion concerning combustion, venting, piping, and other stan­
dard installation practices. Further reference is made to the
ciurrent edition of the American National Standard Z223.1
National Fuel Gas Code.

Each furnace is shipped from the factory completely assem­
bled with multispeed direct-drive blower and wired ready for
counterflow indoor heating installation only. All sizes
feature a printed-circuit board control center with easy-to-

read, low-voltage terminal strip to ensure proper connec­
tions.
The efficiency rating of the furnace is a product thermal
efficiency rating determined under continuous operating
conditions independent of any installed system.

CAUTION:

Do not install furnace in a corrosive or contami­

nated atmosphere. Make sure all combustion and circulating
air requirements listed in "Procedure for Gas-Fired Fur­
naces” are adhered to, in addition to, all local codes and

ordinances.
The design of the counterflow gas-fired furnace is A.G.A. cer­
tified for installation on combustible flooring (with optional

floor base), in alcoves, basements, closets, or utility rooms.
This furnace line is

not

A.G.A. certified for installation in a

mobile home, recreation vehicle, or outdoors.

TABLE i-CLEARANCES (In Inches)

Sizes

050

075 thru 150

Sides—Single-Wall Vent

1

1

Type-B Double-Wall Vent

0

1

Back

0

0

Top of Plenum

1

1

Vent Connector—Single-Wall

6

6

Type-B Double-Wall

1

1

Front—Combustion Air

6

6

Service

30

30

Installation comprises the following:

I. Inspection

II. Location, Ventilation, and Air for Combustion

III. Gas Piping

IV. Venting

All of the above steps are covered in general by the like-num­
bered sections of the "Procedure for Gas-Fired Furnaces”
booklet packaged with the furnace; therefore, these Installa­
tion Instructions will contain only supplementary informa­
tion applicable to installing the furnace.

In addition, the following sections deal specifically with in­
stallation of the 396G:

V. Supply-Air Plenum Installation

VI. Electrical

VII. Sequence of Operation

VIII. Filter

IX. Startup and Adjustment

X. Care and Maintenance

For accessory installation details, refer to applicable in­
stallation literature.

Cancels: 40396DP5-A

and 40396DP6-A

40396DP7-A

1/15/80

I ! '

I" r,

---- - !

.- i

Ipip Í

A78593

Figure 1—Model 396G036075 With Optional

Vent Damper Installed

V.

SUPPLY-AIR PLENUM INSTALLATION

A. Installation on a concrete slab

1. See Figure 2 for dimensions and location of supply-air

opening in furnace bottom.

2. Construct hole in floor per dimensions in Figure 3 eind

Table IV.

3. Place plenum and furnace as shown in Figure 4.

B. Installation on a combustible floor

1. Read Installation Instructions packaged with combusti­

ble floor base.

2. Cut and frame hole in floor per dimensions in Table I of

Installation Instructions packaged with combustible floor
base. If this requires cutting of a floor joist, tie ends of cut

joist into adjacent joists so that proper floor support will be

maintained.

3. Assemble and install combustible floor base per instruc­

tions packaged with base.

4. When completed, combustible floor base, plenum, and

furnace (or coil casing when used) should be installed as
shown in Figure 6.

RDP Company, Division of Carrier Corp.