Table 5—Specifications—Models 48N (Sizes VT042300 thru MT048600)
MODEL
48N
48N
48N
48N
48N
48N
48N
48N
48N
SIZE
VT042300
VT042500
VT042600
LT048300
LT048500
LT048600
MT048300
MT048500
MT048600
Unit Volts—Phase (60 Hz)
208/230—1 208/230—3
460—3
208/230—1 208/230—3
460—3
208/230—1 208/230—3
460-3
Operating Voltage Range
187—253
187—253
414—506
187—253
187—253
414—506
187—253
187—253
414—506
Unit Full Load Amps
26.7
18.2
9.6
27.2
22.1
11.0
27.5
22.1
11.0
Maximum Fuse Size (Amps)
45
30
15
50
40
20
50
40
20
Minimum Ampacity for Wire Sizing*
31.7
21.1
11.1
32.7
26.0
13.1
32.7
26.1
13.1
Minimum Wire Size (75 C Copper)
10
12
14
8
10
14
8
10
14
Maximum Wire Length (Ft.)
75
65
110
95
100
100
95
100
100
Cooling Capacity (Btuh)f
41,500
41,500
41,500
47,500
47,500
47,500
47,500
47,500
47,500
Rated Cooling Airflow (cfm)f
1500
1500
1500
1700
1700
1500
1700
1700
1700
External Static Pressure (In.
water)t
0.15
0.15
0.15
0.20
0.20
0.15
0.20
0.20
0.20
ARI Sound Rating^:
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
8.2
Rated Heating Input (cfm)
120,000
120,000
120,000
80,000
80,000
60,000
100,000
100,000
100,000
Output Capacity (Btuh)**
93,000
96,000
96,000
62,000
64,000
48,000
78,000
80,000
80,000
AFUE(%)**
77.5
—
—
77.5
—
—
77.5
—
—
Rated Heating Airflow (cfm)
1367
1367
1367
1481
1481
1481
1481
1481
,1481
Recommended Minimum Field-
Supplied Filter Size (Sq ln.)tt
Disposable-Type
720
816
816
Cleanable- or High-Capacity Type
480
544
544
(Applicable notes are listed below Table 7.)
Table 6—Specifications—Models 48N (Sizes HT048300 thru MT060600)
MODEL
48N
48N
48N
48N
48N
48N
48N
48N
48N
SIZE
HT048300
HT048500
HT048600
LT060300
LT060500
LT060600
MT060300
MT060500
MT060600
Unit Volts—Phase (60 Hz)
208/230—1 208/230—3
460—3
208/230—1 208/230—3
460—3
208/230—1 208/230—3
460-3
Operating Voltage Range
187—253
187—253
414—506
187—253
187—253
414—506
187—253
187—253
414—506
Unit Full Load Amps
27.5
22.1
11.0
40.8
31.6
14.6
40.8
31.6
14.6
Maximum Fuse Size (Amps)
50
40
20
60
50
25
60
50
25
Minimum Ampacity for Wire Sizing*
32.7
26.0
13.1
48.5
37.0
17.2
48.5
37.0
17.2
Minimum Wire Size (75 C Copper)
10
12
14
8
10
14
8
10
14
Maximum Wire Length (Ft.)
75
65
110
95
100
100
95
100
100
Cooling Capacity (Btuh)t
47,500
47,500
47,500
59,500
59,500
59,500
59,500
59,500
59,500
Rated Cooling Airflow (cfm)t
1700
1700
1700
2000
2000
2000
2000
2000
2000
External Static Pressure (In.
water)t
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
0.20
ARI Sound Ratingf:
8.2
8.2
8.2
8.4
8.4
8.4
8.4
8.4
8.4
Rated Heating input (cfm)
120,000
120,000
120,000
80,000
80,000
80,000
100,000
100,000
100,000
Output Capacity (Btuh)**
93,000
96,000
96,000
62,000
64,000
64,000
78,000
80,000
80,000
AFUE (%)**
77.5
_
—
77.5
—
—
77.5
—
—
Rated Heating Airflow (cfm)
1367
1367
1367
1481
1481
1481
1646
1646
1646
Recommended Minimum Field-
Supplied Filter Size (Sq ln.)tt
Disposable-Type
816
960
960
Cleanable- or High-Capacity Type
544
640
640
(Applicable notes are listed below Table 7.)
Table 7—Specifications- - Models 48N (Sizes HT060300 thru HT060600)
MODEL
48N
48N
48N
SIZE
HT060300
HT060500
HT060600
Unit Volts—Phase (60 Hz)
208/230—1
208/230—3
460—3
Operating Voltage Range
187—253
187—253
414—506
Unit Full Load Amps
40.8
31.6
14.6
Maximum Fuse Size (Amps)
60
50
25
Minimum Ampacity for wire Sizing*
48.5
37.0
17.2
Minimum Wire Size (75 C Copper)
10
12
14
Maximum Wire Length (Ft.)
75
65
110
Cooling Capacity (Btuh)t
59,500
59,500
59,500
Rated Cooling Airflow (cfm)t
2000
2000
2000
External Static Pressure (in. water)t
0.20
0.20
0.20
ARI Sound Ratingt
8.4
8.4
8.4
Rated Heating Input (Btuh)**
120,000
120,000
120,000
Output Capacity (Btuh)**
93,000
96,000
96,000
AFUE(%)**
77.5
—
—
Rated Heating Airflow (cfm)
1975
1975
1975
Recommended Minimum Field-
Supplied Filter Sizeft
Disposable-Type
960
Cleanable- or High-Capacity Type
640
*lf other than 75 C copper wire is used, determine size from unit ampacity and the National Electrical Code. Voltage drop of wire must be less than 2%
of unit rated voltage.
fRated in accordance with U.S. Government D.O.E. test procedures and/or ARI Standard 210.
tRated in accordance with ARI Standard 270.
**The capacity ratings of single-phase units are in accordance with U.S. Government D.O.E. test procedures and/or A.G.A. certification requirements. For
3-phase units, the efficiency rating is a product thermal efficiency rating determined under continuous operating conditions, independent of any
installed system.
ttRequIred filter areas shown are based on the larger of the ARI-rated cooling airflow or the heating airflow at a velocity of 300 ft/min for disposable type
or 450 ft/mln for hIgh-capacIty type. Air filter pressure drop must not exceed 0.08 in.-water.
8