I. refrigerant circuit, J. gas input, K. evaporator airflow – Carrier 48N User Manual
Page 22: L. metering device servicing, M. liquid line strainer
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
occurred, check each electrical component with the proper
electrical instrumentation. Refer to the unit wiring label
when making these checkouts.
NOTE:
Refer to the heating and/or cooling sequence of oper
ation in this publication as an aid in determining proper con
trol operation.
I. Refrigerant Circuit
Inspect all refrigerant tubing connections and the unit base
for oil accumulations annually. Detecting oil generally indi
cates a refrigerant leak.
If oil is detected or if low cooUng performance is suspected,
leak-test all refrigerant tubing; using an electronic leak-
detector, halide torch, or liquid-soap solution. If a refriger
ant leak is detected, see Step 7, part B, “Refrigerant
Leaks,” in this publication.
If no refrigerant leaks are found and low cooling perform
ance is suspected, see Step 9, part B, “Checking and
Adjusting Refrigerant Charge,” in this pubhcation.
J. Gas Input
The gas input does not require checking unless improper
heating performance is suspected. If a problem exists, refer
to Step 8 of this publication.
K. Evaporator Airflow
The heating and/or cooling airflow does not require checking
unless improper performance is suspected. If a problem
exists, be sure that all supply- and return-air grilles are open
and free from obstructions, and that the air filter is clean.
When necessary, refer to Step 9, part C, of this pubhcation
to check the system airflow.
L. Metering Device Servicing
See Fig. 15 for metering device components. The piston has
a refrigerant metering orifice through it. The retainer forms
a seahng surface for hquid hne flare connection. To check,
clean or replace piston:
1. Shut off power to unit.
2. Remove refrigerant from unit using approved refriger
ant removed methods.
3. Remove hquid line flare connections from metering
device.
4. Note position of arrow on metering device body with
respect to unit.
5. PuU retainer out of body. Be careful not to scratch flare
seahng surface. If retainer does not puU out easily,
carefuhy use locking phers to remove retainer. Replace
scratched or damaged retainer.
6. Slide piston out by inserting a smah soft wire through
metering hole (18-gage thermostat wire). See that
metering hole, seahng surface around piston cones and
fluted portion of piston are not damaged.
7. Chart on unit access panel ihustrates proper arrange
ment and size of piston. See Table 17 for piston sizes.
8. Clean piston refrigerant metering orifice.
9. Replace reteuner 0-riug Part No. is 99CC501052.
M. Liquid Line Strainer
The Liquid Line Strainer (to protect metering device), is
made of wire mesh and located in the hquid hne on inlet
side. Strainer is pressed into the hne. Remove strainer by
threading a No. 10 sheet metal screw into strainer and puU-
ing the screw with phers.
22