beautypg.com

Condensate disposal, Asse coni loca stac top blo\ c – Carrier 48GH User Manual

Page 3

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Unit must remain in an upright position during all

rigging and moving operations. Unit must be level

for proper condensate drainage; therefore, ground-
level pad or field-supplied mounting curb must be
level before setting unit in place.

ROOFTOP INSTALLATION

CAUliON: When instalHng nnit on a rooftop^
he sare roof support tits odditionaJ weight.

Refer to Prodìtct Data Digest to ohiaia total

weight aad corner weight Istformailon,

When installing a Model 4»GH/GL end-

discharge unit with a field-supplied downflow
plenum, a field-supplied roof-mounting curb must
be installed on and flashed into roof before unit
installation.

When installing a Model 48GH/GL end-

discharge unit without a downflow plenum, place
unit on a level base that provides proper support. On
flat roofs be sure that unit is located at least 4 in.
above highest expected water level on roof to pre­
vent flooding. Consult local codes for additional

installation requirements.

GROUND-LEVEL

INSTALLATION

Place

unit on a solid, level concrete pad that is a minimum
of 4 in. thick and that extends approximately 2 in.
beyond casing on all 4 sides of unit. Do not secure
unit to pad except when required by local codes.

CLEARANCES — The required minimum oper­
ating and service clearances are shown in Fig. 1.

Condenser fan discharges thru top of unit. En­

sure that fan discharge does not recirculate to
condenser coil. Do not locate unit in either a corner
or under a complete overhead obstruction. Mini­
mum clearance under a partial overhang (such as a

normal house roof overhang) is 3 ft above vent cap.

Do not locate unit where water, falling ice or snow

from an overhang or roof will damage or flood the
unit. Do not locate unit where grass, shrubs, or
other plants will interfere with airflow either into
or out of unit.

Condensate Disposal

NOTE: Ensure that condensate-water disposal
methods comply with local codes, restrictions and
practices.

Models 48GH/GL dispose of condensate water

thru a 3/4-in. MPT drain fitting. See Fig. 1 for
location.

Install a 3-in. trap at drain fitting to ensure

proper drainage. See Fig. 3. Make sure trap outlet
is at least 2 in. lower than unit drain pan connection
to prevent pan from overflowing. Prime trap with
water.

If the installation requires draining condensate

water away from the unit, connect a drain tube
using a minimum of 7/8-in. OD copper tubing.

3/4

not
at a

run.

C

roo]

ont(

Wh

awa

FROM

Ver

asse

coni

loca

stac

top

blo\

C

S

h

m

tì<

Table 1 — Installation C

MODEL 48

GL018

GL024

GH024

GL030

GH030

GL036

GL036

GL036

GH036

GH036

GL042

GL042

SERIES

300

300

300

300/310

300/310

300/310

500/510

600/610

300/310

500/510

300

500

DIMENSIONS (ft-in )

A

4-5-5/S

4-5- 5/8

5- 5-5/8

B

2-6-3/8

3-4-3/8

3- 8-5/8

c

3-2-1/8

3-5- 1/8

3-10-1/8

D

1- 4

1- 7

2- 0

E

1- 4

1-1- 1/4

1- 1-1/4

F

0-7-1/4

*, 0-8-7/8

0- 8-7/8

G

0-1-3/32

0-1- 3/8

0- 1-3/8

H

0- 11

0-10

0-10

J

1-10-5/8

K

3-7-3/8

4-0-3/8

4- 1

FIELD-SUPPLIED FILTER

SIZE (sq in )•
Standard Disposable Type

289

396

396/433t

522

522

576

576

576

583/722t

583/722t

672

672

Cleanable- or

High-Capacity Type

188

257

257/281t

339

339

374

374

374

379/469t

379/469t

437

437

OPERATING WT (lb)

320

325

375

375

375

380

380

380

475

475

420

420

SHIPPING WT (lb)

330

335

385

385

385

390

390

390

485

485

430

430

HEATING INPUTt (Stub)

Min

40,000

40,000

60,000

40,000

60,000

60,000

60,000

60,000

100,000

100,000

60,000

60,000

Max

50,000

50,000

75,000

50,000

75,000

75,000

75,000

75,000

125,000

1 25,000

75,000

75,000

COOLING AIRFLOW (Cfm)

600

825

825

1088

1088

1200

1200

1200

1215

1215

1400

1400

EXTERNAL STATIC

PRESSURE (in wg)

0 10

0 10

0 10

0 15

0 15

0 15

0 15

0 15

0 15

0 15

0 15

0 15

•Recommended, field-supplied air filter areas shown are based on either cooling airflow at a velocity of 300 ft per

minute or heating airflow at a temperature of 60 F, depending on whichever value is larger Air filter pressure drop
should not exceed 0 08 in wg for unit to produce rated cooling performance

tWhen Models 48GH024 or GH036 are installed for operation at minimum rated heating input, recommended

minimum air filter area is the smaller sq in figure shown for each type of filter Larger figures shown are mini-

mum rei

heating

|AII units

orifices

1