Fig. 8 — burner flames – Carrier 48GH User Manual
Page 11
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".
Proceed as follows to measure and change
manifold pressure:
a. Turn off gas to unit.
b. Remove pipe plug on gas valve outlet identified
as PRESS TAP, then connect manometer at
this point.
c. Turn on gas to unit and start heating section.
d. Measure and change manifold pressure with all
burners fired to obtain desired gas input.
e. Turn off gas to unit, remove manometer from
gas valve, and replace pipe plug.
ADJUSTING
BURNER
AIR
SHUTTERS
After burners have operated at full input for at least
10 minutes, adjust primary air to each burner to
ensure optimum heating performance. Make these
adjustments when unit is being installed and during
routine maintenance inspections at beginning of
each heating season. Be sure that each burner is
clean and free of deposits before adjusting primary
air.
The primary air to each burner is regulated by
burner air shutter on each burner. See Eig. 8 for
location of burner air shutter. With all burners
operating, adjust primary air to each burner as
follows:
1. Loosen locking screw that secures air shutter
in place on burner, then partially close air shutter
until a slight yellow tip appears on top of burner
flames.
2. Open air shutter very slowly until yellow tip just
disappears, then secure air shutter in place with
locking screw.
3. Repeat steps 1 and 2 for each burner.
After air shutter adjustments have been com
pleted, observe that flames on each burner are light
blue and “soft” in appearance, and that flames are
same height along the entire length of each burner.
See Fig. 8.
AIR
SHUTTER
MANIFOLD
Fig. 8 — Burner Flames
BLOWER HEAT-RELAY OPERATION — Heat
relay (see Fig. 6 and unit wiring diagram) is located
in control box and adjusts to permit either longer or
shorter OFF cycles. The ON cycle automatically
adjusts as OFF cycle changes. Adjusting lever on
relay is factory-set at center position to provide
optimum performance for most installations. On
unusual installations, or where line voltage is
considerably above or below rated voltage, length
of time blower remains on may require increasing or
decreasing. To increase blower operation time,
move adjusting lever toward right-hand position.
In this position, control makes contact sooner and
"takes maximum time to break contact. To decrease
blower operation time, move lever toward left-
hand position.
AIRFLOW AND TEMPERATURE RISE —^
Temperature rise is temperature difference between
air in return duct and air in discharge duct at unit.
Heating section of each size of unit is designed and
approved for heating operation within temperature
rise range stamped on unit rating plate.
Table 4 shows the approved temperature rise
range for each unit, and air delivery (cfm) at various
temperature rises for both A.G.A.-certified gas
input ratings. Heating operation airflow must
produce a temperature rise that falls within
approved range.
Table 4 — Air Delivery (Cfm) at Indicated Temperature
Rise and Rated Heating Input
MODEL NO
HEATING
TEMPERATURE RISE (F)
48
INPUT
.
-
------
--
- ___
-
- “ " —
(Btuh)
35
37 5
40
42 5
45
47 5
50
52 5
55
57 5
60
62.5
65
67 5
70
75
GL018,024,
40,000*
794
741
694
654
617
585
556
529
505
483
463
444
427
397
383
370
030
50,000
1032
963
903
850
802
760
722
68"8^
657
628
602
578
556
535
516
498
481
GH024,030
60,000'
1190
1111
1042
980
926
877
833
794
758
725
694
667
641
617
595
575
556
GL036,042
75,000
1548
1444
1354
1275
1204
1140
1083
1032
985
942
903
867
833
802
774
747
722
GH042
80,000*
1587
1481
1389
1307
1235
1170
1111
1058
1ÒÌÒ
966
926
889
855
823
794
766
741
GL048
100,000
2063
1926
1806
1699
1605
1520
1444
1376
1313
1256
1204
1156
1111
1070
1032
996
963
GH036,048
100,000*
1984
1852
1736
163£^
1543
1462
1389
1323
1263
1208
1157
1111
1068
1029
992
958
926
GL060
125,000
2579
2407
2257
2124
2006
1901
1806
1720
1641
1570
1505
1444
1389
1337
1290
1245
1204
GH060
1 20,000*
2381
2222
2083
1961
1852
1754
1667
1587
1515
1449
1389
1333
1282
1235
1190
1149
nil
150,000
3095
2889
2708
2549
2407
2281
2167
2063
1970
1884
1806
1733
1667
1605
1548
1494
1444
‘These inputs are the minimum rated inputs using factory-installed burner
orifices Higher inputs shown for each size are the maximum rated inputs
using field-installed, optional burner orifices that are indicated on unit
rating plate
NOTE:
Models
48GL018,024,036;
48GH024,030
have
an
approved
tem
perature rise range of 35 to 75 F All other units have an approved tempera
ture rise range of 45 to 75 F
11