beautypg.com

Cooling section start-up and adjustments – Carrier 48GH User Manual

Page 12

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Refer to Cooling Section Start-Up and Adjust­

ments INDOOR AIRFLOW AND AIRFLOW
ADJUSTMENTS of these instructions to adjust
heating airflow when required.

LIMIT AND PRESSURE SWITCHES — Furnace
limit switch (see Fig. 9) closes gas valve if leaving-air
temperature exceeds 175 F.

Normally closed limit switch completes control

circuit thru pigtail lead W to gas valve. See Fig. 9.

Should the leaving-air temperature rise to 175 F,
switch opens and W control circuit breaks. Any
interruption in W control circuit instantly closes
gas valve and stops gas flow to burners and pilot.
The indoor fan motor continues to run until time-
delay sequence of time delay relay (heating) is
completed.

When air temperature at limit switch drops to the

low-temperature setting of limit switch, switch
closes and completes W control circuit. Electric-
spark ignition system cycles and unit returns to

normal heating operation.

Pressure switch (Fig. 9) is required only when

unit operates on LP (propane) gas.

Cooling Section Start-Up and Adjustments

CAUTION:

Comp^lete

required

procedufes

given in Unit Preparation section before start­
ing imit.

Do not yumper any safety devices when oper­

ating unit.

Do not operate compressor when outdoor

temperature is beJow 55 F.

To prevent rapid cycling of compressor.

Time Gnard H is supplied as standard

equipment.

CHECKING COOLING CONTROL OPERA­
TION — Start and check unit for proper cooling

control operation as follows:

1. Place room thermostat selector swtich in OFF

position. Observe that blower motor starts when
fan switch is placed in ON position and shuts
down when fan switch is placed in AUTO,
position.

2. Place selector switch in COOL position and fan

switch in AUTO, position. Set cooling control

below room temperature. Observe that com­
pressor, condenser fan, and evaporator blower

motors start. Observe that cooling cycle shuts
down when control setting is satisfied.

3. When using an automatic changeover room

thermostat, place both selector and fan switches
in AUTO, position. Observe that unit operates

in heating mode when temperature control is
set to call for heating (above room temperature)
and operates in cooling mode when temperature
control is set to call for cooling (below room
temperature).

CHECKING

AND

ADJUSTING

REFRIG­

ERANT CHARGE — Refrigerant system is fully

charged with R-22 refrigerant, tested, and factory
sealed. For most applications, factory charge is the
correct amount for best performance.

NOTE: Adjustment of refrigerant charge is not
required unless unit is suspected of not having
proper R-22 charge. For all applications, correct

R-22 charge for best performance is charge that

results in a suction gas superheat of 5 F at com­
pressor inlet when unit is operating at ARI rating

conditions of 95 F db outdoor and 80 F db/67 F wb
indoor.

An

operating

pressure/temperature

tag

is

fastened inside the compressor compartment. Use
tag to approximate charge if ARI rating conditions
cannot be obtained when evaluating the refrigerant
charge by checking operating pressures and tem­

peratures. See Table 5. This method of evaluating
ensures that an optimum refrigerant charge is in
system when system conditions and components are
normal; however, adjusting refrigerant charge does
not solve or fix system abnormalities.

Amount of refrigerant charge affects how effi­

ciently and economically unit operates. An over­
charged or undercharged unit leads to diminished

cooling efficiency, high operating costs and the
possibility of premature compressor failure.

CAUTION;

When

evaiuatiiig

refrigsiant

charge,, an indicated adjustiuent to specified
factory charge must always be very ouoimai. if a
substaotial adjustment is oidk».ted:, ass. ab-
rtoruial conditioa existe somewbere in cooHiig

system; such as msufficient airflow across either
coil or both coils.

NOTE: For best results, evaluate refrigerant charge
when outdoor temperature is 65 F or higher.

Proceed as follows to evaluate system perform­

ance and refrigerant charge:

1. Remove caps from low- and high-pressure

service fittings.

2. Attach low- and high-side pressure gage hoses

to low- and high-pressure service fittings,

respectively. Hoses must have valve core de­

pressors. Gages must be calibrated for accuracy.

3. Set room thermostat below room temperature to

start cooling operation. Allow unit to operate
until conditions stabilize and pressures level out.

4. Determine and record these conditions:

a. Low- and high-side pressures.
b. Dry-bulb
temperature of inlet air at outdoor

condenser coil.

c. Wet-bulb temperature of inlet air at indoor

evaporator coil.

d. Suction gas temperature at compressor inlet if

unit is operating at ARI standard rating con­
ditions indicated on operation pressure/

temperature tag.

12