Table 6—field charging table—fixed restrictor – Carrier 50QQ User Manual
Page 10
Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

Table 6—Field Charging Table—Fixed Restrictor
HEATING OPERATING PRESSURES PSIG (Pressures at High and Low Side Service Ports)
MODEL
INDOOR
OUTDOOR TEMPERATURE (F) DRY BULB
50QQ
DRY BULB (F)
60
50
40
30
20
10
0
-10
65
High
217
202
189
178
168
157
149
140
Low
77.2
65
53.8
43.7
34.7
26.8
19.7
12.6
018
70
High
232
217
203
192
181
169
158
147
Low
77.8
65.4
54.2
44
35
27
19.8
12.9
75
High
248
232
218
205
195
184
174
165
Low
78.4
65.9
54.9
44.4
35.2
27.3
21.1
13.2
65
High
219
204
191
179
171
161
150
139
Low
72.1
60.4
50.2
40.8
32.5
25.1
18.4
11.7
024
70
High
235
219
205
194
183
174
164
154
Low
72.6
60.9
50.5
41.2
32.9
25.4
18.7
12
75
High
251
235
221
209
196
185
176
165
Low
73.2
61.4
51
41.6
33.2
25.6
18.9
12.1
65
High
219
203
190
179
168
153
150
141
Low
70.5
58.9
48.7
39.8
31.9
24.7
18.1
11.6
030
70
High
235
219
205
195
184
170
158
145
Low
71.1
59.4
49.2
40.2
32.2
24.9
18.3
11.7
75
High
250
235
222
208
196
186
176
167
Low
71.5
59.9
49.7
40.6
32.5
25.2
18.6
11.9
65
High
218
202
190
180
172
161
152
142
Low
70.9
59.1
48.8
39.8
31.9
24.6
18.1
11.6
036
70
High
231
216
202
192
186
174
163
153
Low
71.4
59.6
49.3
40.1
32.2
24.9
18.3
11.7
75
High
246
230
216
205
198
187
178
169
Low
72
60.1
49.7
40.5
32.5
25.2
18.5
11.9
65
High
212
197
184
172
162
153
144
135
Low
69.6
58.1
48
39.2
31.5
24.4
18
11.6
042
70
High
226
211
197
185
174
164
155
145
Low
70.2
58.7
48.6
39.7
31.9
24.7
18.3
11.8
75
High
241
225
211
198
187
176
165
155
Low
70.7
59.2
49.1
40.2
32.3
25
18.5
12.1
65
High
315
200
186
174
163
154
145
136
Low
67.7
56.5
46.7
38.1
30.5
23.7
17.5
11.3
048
70
High
229
213
200
187
175
164
154
144
Low
68.3
57.1
47.2
38.6
31
24
17.8
11.5
75
High
243
227
213
200
189
177
167
156
Low
69
57.7
47.7
39
31.4
24.3
18.1
11.8
65
High
214
199
185
174
163
155
145
136
Low
65.2
54.2
44.7
36.4
29
22.5
16.6
10.8
060
70
High
228
213
199
187
175
164
155
146
Low
65.8
54.8
45.2
36.9
29.5
22.9
16.8
10.8
75
High
243
227
213
200
189
178
168
158
Low
66.4
55.4
45.7
37.3
29.9
23.2
17.1
11.0
NOTE: Add charge if pressures are low Bleed out charge if pressures are high. Allow ± 5 psig tolerance on high-side pressure.
B
COOLING DESIRED SUPERHEAT TEMP (F)
(Measured at Low-Side Service Port)
OUTDOOR
DBT
EVAPORATOR AIR INLET WBT (F)
DGT(F)
54
56
58
60
62
64
66
68
70
72
74
76
60
12
15
18
21
24
27
30
33
36
38
40
43
65
10
13
16
19
21
24
27
30
33
36
38
41
70
7
10
13
16
19
21
24
27
30
33
36
39
75
if
6
9
12
15
18
21
24
28
31
34
37
60
*
*
5
8
12
15
18
21
25
28
31
35
85
■¥
*
«
*
8
11
15
19
22
26
30
33
90
*
*
*
*
5
9
13
16
20
24
27
31
95
♦
*
*
*
*
6
10
14
18
22
25
29
100
♦
*
«
*
*
*
8
12
15
20
23
27
105
♦
*
♦
*
*
♦
5
9
13
17
22
26
110
«
*
*
«
*
*
*
6
11
15
20
25
115
*
♦
*
«
*
*
*
*
8
14
18
23
REQUIRED SUCTION TUBE (F) VS. DESIRED
SUPERHEAT (F)
(Measured at Low-Side Service Port)
DESIRED
SUPERHEAT
*Do not attempt to charge system under these conditions or refrigerant
slugging may occur
NOTE: Add charge if actual superheat temperature is higher than chart
value. Remove if lower Allow ± 3 F for tolerance.
Unit is factory charged with R-22 in accordance with amount shown
on rating plate. This chart is intended for usage when minor unit
charge adjustments are required. For large charge adjustments, evac
uate unit and weigh in charge according to unit rating plate. Best per
formance will be achieved when unit operates with a suction gas
superheat at compressor inlet of 5 F at normal rating conditions of
Air Conditioning and Refrigeration Institute (ARI). This chart may be
used to approximate the charge if ARI rating conditions cannot be
obtained. ARI rating conditions are 95 F db outdoor. 89 F and 67 F
wb indoor. See Table 4 for required indoor airflow rates. Charge unit
with outdoor fan operating only on high speed.
SUCTION OR LOW-SIDE PRESSURE (psig)
AT SERVICE PORT
TEMP (F)
61.5
64.2
67.1
70
73
76
79.2
82.4
85.7
0
35
37
39
41
43
45
47
49
51
2
37
39
43
43
45
47
49
51
53
4
39
41
43
45
47
49
51
53
55
6
41
43
45
47
49
51
53
55
57
8
43
45
47
49
51
53
55
57
59
10
45
47
49
51
53
55
57
59
61
12
47
49
51
53
55
57
59
61
63
14
49
51
53
55
57
59
61
63
65
16
51
53
55
57
59
61
63
65
67
18
53
55
57
59
61
63
65
67
69
20
55
57
59
61
63
65
67
69
71
22
57
59
61
63
65
67
69
71
73
24
59
61
63
65
67
69
71
73
75
26
61
63
65
67
69
71
73
75
77
28
63
65
67
69
71
73
75
77
79
30
65
67
69
71
73
75
77
79
81
32
67
69
71
73
75
77
79
81
83
34
69
71
73
75
77
79
81
83
85
36
71
73
75
77
79
81
83
85
87
38
73
75
77
79
81
83
85
87
89
40
75
77
79
81
83
85
87
89
91
NOTE: Measure suction tube (F) with accurate superheat thermocouple
or thermistor-type thermometer.
FINAL DISPOSAL: CAUTION—CAREFULLY RELIEVE REFRIGERANT
PRESSURE WITHIN UNIT BEFORE FINAL DISPOSAL
10