beautypg.com

Warnock hersey, Step 7 — make outdoor-air inlet adjustments, Fig. 12 — 25% outdoor-air section details – Carrier 50HJ015 User Manual

Page 8: Step 7 — make outdoor-air inlet, Adjustments, Step 8 — install outdoor-air hood, Table 2 — electrical data

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 2 — Electrical Data

UNIT
50HJ

V-PH-HZ

VOLTAGE

RANGE

COMPRESSOR

CONDENSER

FAN MOTOR

EVAPORATOR

FAN MOTOR

ACCESSORY/OPTIONAL

ELECTRIC HEATERS*

POWER SUPPLY

No. 1

No. 2

Min

Max

RLA

LRA

RLA

LRA

Qty

FLA

Hp

FLA

FLA

kW

MCA^

MOCPt

015

208/230-3-60

187

253

49 3

191

-

-

2

77

3

105

39/ 45

72/ 82

117/135

14/19

26/34
42/56

88/ 88
88/ 88

103/116

159/148

100/100

100/100
110/125

175/175

460-3-60

414

508

22 1

86

-

-

2

33

3

48

18
39

66

15

32
55

39
39
55

72

45

45
60

80

575-3-60

518

632

179

69

-

-

2

26

3

3 9

37

37

32

52

35
60

024

208/230-3-60

187

253

43 9

170

43 9

170

2

54

(ea)

I'k

24 2/22 0

72/ 82

117/135

156/180**

26/34
42/56

56/75**

134/132
134/132
177/163

186/208**

175/175

175/175
200/175

200/225**

460-3-60

414

508

199

77

199

77

2

27

(ea)

7'/г

11 0

39

66

96**

32

55

80**

62
62
80

110**

80
80

90

110**

575-3-60

518

632

15 9

62

159

62

2

34

(ea)

7'M

90

-

-

52

60

LEGEND

Full Load Amps

Heating, Air Conditioning and Refrigeration
Looked Rotor Amps

Minimum Circuit Amps

Maximum Overcurrent Protection
Nationai Eiectrioai Code
Rated Load Amps

•Heater capacity (kW) is based on heater voitage of 208 v, 240 v, 480 v and

575

V.

if power distribution voltage to unit varies from rated heater voltage,

heater kW will vary accordingly This is the maximum size permissible; smaller
fuse size may be used where conditions permit

tFuse or HACR circuit breaker

"Heaters are field installed only

FLA

-

HACR

-

LRA

-

MCA

-

MOCP

-

NEC

-

RLA -

NOTES
1

In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker The Canadian units may
be fuse or circuit breaker
MCA calculation for units with electric heaters over 50 kW

= (1.25

X

IFM amps) + (1 00 x heater FLA).

Warnock Hersey

Table 3 — Heat Anticipator Settings

UNIT

VOLTAGES

kW

STAGE 1

STAGE 2

14/17

40

_

208/230

26/31

40

40

50HJ

42/52

66

40

15

40

_

U1 b

460

30

40

40

51

40

66

575

37

40

.66

26/31

40

66

208/230,575-3-60

42/52

.66

40

50HJ

56/69

66

66

024

30

40

40

460-3-60

51

40

66

73

66

66

Step 7 — Make Outdoor-Air Inlet
Adjustments

MANUAL OUTDOOR-AIR DAMPER - All units
(except those equipped with a factory-installed economizer)
have a manual outdoor-air damper to provide ventilation
air. Damper can be preset to admit up to 25% outdoor air
into retum-air compartment. To adjust, loosen securing screws
and move damper to desired setting Then retighten screws
to .secure damper (Fig. 12).

OPTIONAL FACTORY-INSTALLED ECONOMIZER
Economizer Motor Control Module (Fig, 13-15) — Set to
the "D" setting (Fig. 14) The control module is located on
the economizer motor. See Fig, 13 and 15.
Damper Vent Position Setting

1. Set fan switch at ON position (continuous fan operation)

and close night switch if used.

2. Set system selector switch to OFF position.
3. Turn adjustment screw slowly until dampers assume de­

sired vent position. Do not manually operate econo­
mizer motor since damage to motor will result.

NOTE; Refer to accessory installation instructions in­
cluded with the field-installed economizer for installation

information. Also see Accessory Field-Installed Econo­
mizer Adjustment section on page 10.

Step 8 — Install Outdoor-Air Hood

— The same

type of factory-installed hood is used on units with 25% air
ventilation and units with an economizer.
NOTE; The hood top panel, upper and lower filter retain­
ers, hood drain pan, baffle (024 only), and filter support
bracket are secured opposite the condenser end of the unit.
The screens, hood side panels, remaining section of filter
support bracket, seal strip, and all other hardware are in a
package located inside the return-air filter access panel
(Fig. 16)

1. Attach seal strip to upper filter retainer. See Fig. 17.

2. Assemble hood top panel and side panels, upper filter

retainer, and hood drain pan (Fig. 18)

3. Secure lower filter retainer and long piece of filter sup­

port bracket to unit. See Fig. 18. Leave screws on 024
units loose

4. 50HJ024 Units Only; Slide baffle behind lower filter re­

tainer and tighten screws.

5. Loosen sheet metal screws for base unit top panel lo­

cated above outdoor-air inlet opening.

25% ADJUSTABLE
AIR DAMPER

BASE

■ UNIT

SECURING SCREWS

Fig. 12 — 25% Outdoor-Air Section Details

t

I