background image

Table 5 — Fan Performance Data, 50HJ015 Units

Ф

EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(Cfm)

0.2

0.4

0.6

0.8

1.0

1.2

1.4

1.6

1.8

2.0

Rpm

Watts

Rpm Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

3750

732

684

848

835

949

977

1041

1119

1124

1270

1194

1430

1247

1599

1274

1767

~

4000

764

799

876

968

974

1110

1065

1261

1146

1412

1221

1572

1284

1750

1331

1927

1357 2105

4250

797

933

904

1101

1001

1261

1089

1412

1170

1581

1244

1741

1312

1909

1369 2096

1413 2282

1440 2469

4500

831

1075

934

1252

1028

1430

1113

1581

1193

1750

1267

1918

1335 2096

1398 2282

1451 2478

1493 2673

4750

865

1226

965

1421

1056

1607

1139

1767

1217

1945

1290 2123

1358 2300

1422 2487

1480 2682

1531 2877

5000

900

1403

996

1599

1084

1803

1166

1980

1241 2149

1314 2336

1381 2522

1444 2709

1504 2904

5250

935

1590

1028

1794

1112 2007

1193 2202

1266 2371

1338 2567

1405 2762

1468 2948

5500

971

1794

1060 2007

1142 2229

1221 2433

1294 2629

1362 2806

1429 3011

5750

1007 2016

1093 2238

1173 2469

1249 2682

1321 2895

6000

1044 2256

1126 2487

1205 2718

1277 2948

6250

1080 2513

1159 2753

1236 2993

LEGEND

Watts

— Input Watts to Motor

NOTES:
1, Factory shipped fan speed is 1092 rpm. The range of the stand­

ard evaporator-fan motor is 978 to 1285 rpm. Other rpms may
require a field-supplied drive.

2 Static pressure iosses (i.e., economizer, eiectric heater) must be

added to external static pressure before entering Fan Perfor­
mance table.

3. To

convert

watts to bhp, use the following equation:

„Watts X motor efficiency

^

746

Motor efficiency:

Horsepower — Maximum Continuous Watts:

0 84

3 hp - 3065

4 Interpolation is permissible Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and casing

losses.

6. Extensive motor and drive testing on these units ensures that

the full range of the motor can be utilized with confidence. Using
your fan motors up to the watts rating shown will not result in nui­

sance tripping or premature motor failure Unit warranty will not
be affected.

Table 6A — Fan Performance Data — 50HJ024, 208/230-V and 575-V Units

EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(Cfm)

0.2

0.4

0.6

0.8

1.0

1.2

1.3

1.4

1.6

1.8

Rpm Watts

Rpm Watts

Rpm Watts

Rpm Watts

Rpm Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm Watts

Rpm Watts

6,000

702

1428

796

1723

884 2025

965 2339

1041 2669

1115 3018

1150 3201

1186 3385

1255 3771

1322 4175

6,500

747

1757

835

2073

919 2394

997 2725

1070 3069

1140 3429

1174 3617

1208 3805

1274 4198

1338 4609

7,000

792 2138

877 2476

957 2816

1031 3165

1102 3525

1169 3898

1201 4091

1233 4285

1296 4687

1358 5106

7,500

838 2571

918 2929

996 3290

1067 3658

1135 4035

1199 4422

1230 4622

1262 4822

1322 5235

1381 5662

8,000

885 3060

962 3440

1036 3822

1105 4209

1170 4604

1232 5008

1262 5180

1292 5422

1350 5847

1407 6286

8,500

932 3610

1005 4011

1077 4414

1143 4821

1206 5234

1266 5655

1295 5870

1324 6085

1380 6524

1435 6975

9,000

980 4223

1050 4647

1119 5071

1183 5498

1244 5930

1302 6369

1330 6592

1359 6816

1413 7270

1466 7735

9,500

1028 4904

1096 5350

1162 5796

1224 6243

1283 6695

1340 7152

1367 7384

1394 7616

10,000

1077 5655

1141 6123

1205 6591

1266 7059

1323 7531

LEGEND

Watts

— Input Watts to Motor

NOTES-
1. Factory shipped fan speed is 1287 rpm Other rpms may require

a field-supplied drive.

2. Static pressure losses (i e., economizer, electric heater) must be

added to external static pressure before entering Fan Perfor­
mance table

3. To convert watts to bhp, use the following equation:

„Watts

X

motor efficiency

^

746

Motor efficiency:

Horsepower — Maximum Continuous Watts:

0.87

71/2

hp-7915

4 Interpolation is permissible Do not extrapolate.
5. Fan performance is based on wet coils, clean filters, and casing

losses.

6. Extensive motor and drive testing on these units ensures that

the full range of the motor can be utilized with confidence. Using
your fan motors up to the watts rating shown will not result in nui­
sance tripping or premature motor failure. Unit warranty will not
be affected.

Table 6B — Fan Performance Data — 50HJ024, 460-V Units

EXTERNAL STATIC PRESSURE (in. wg)

AIRFLOW

(Cfm)

0.2

0.4

0.6

0.8

1.0

1.2

1.3

1.4

1.6

1.8

Rpm Watts

Rpm Watts

Rpm Watts

Rpm

Watts

Rpm Watts

Rpm Watts

Rpm

Watts

Rpm

Watts

Rpm

Watts

Rpm Watts

6,000

702

1428

796

1723

884 2025

965

2339

1041 2669

1115 3018

1150 3201

1186 3385

1255 3771

1322 4175

6,500

747

1757

835 2073

919 2394

997

2725

1070 3069

1140 3429

1174 3617

1208 3805

1274 4198

1338 4609

7,000

792 2138

877 2476

957 2816

1031 3165

1102 3525

1169 3898

1201 4091

1233 4285

1296 4687

1358 5106

7,500

838 2571

918 2929

996 3290

1067 3658

1135 4035

1199 4422

1230 4622

1262 4822

1322 5235

1381 5662

8,000

885 3060

962 3440

1036 3822

1105 4209

1170 4604

1232 5008

1262

5180

1292 5422

1350 5847

1407 6286

8,500

932 3610

1005 4011

1077 4414

1143 4821

1206 5234

1266 5655

1295

5870

1324 6085

1380 6524

1435 6975

9,000

980 4223

1050 4647

1119 5071

1183 5498

1244 5930

1302 6369

1330

6592

1359 6816

1413 7270

1466 7735

9,500

1028 4904

1096 5350

1162 5796

1224 6243

1283 6695

1340 7152

1367 7384

1394 7616

1447 8088

10,000

1077 5655

1141 6123

1205 6591

1266 7059

1323 7531

1378 8007

1404 8248

1431

8489

LEGEND

Watts

— Input Watts to Motor

NOTES:
1 Factory shipped fan speed is 1287 rpm. Other rpms may require

a fieid-supplied drive.

2. Static pressure losses (i.e , economizer, electric heater) must be

added to external static pressure before entering Fan Perfor­
mance table

3 To convert watts to bhp, use the following equation:

_ Watts X motor efficiency

746

Bhp

Motor efficiency:

Horsepower — Maximum Continuous Watts

0 87

7

V

2

hp - 8640

4 Interpolation is permissible. Do not extrapolate.
5 Fan performance is based on wet coils, clean filters, and casing

losses.

6. Extensive motor and drive testing on these units ensures that

the fuli range of the motor can be utilized with confidence. Using
your fan motors up to the watts rating shown will not result in nui­

sance tripping or premature motor faiiure. Unit warranty wili not
be affected.