beautypg.com

Cd [i, 3 qp – Carrier 30GA User Manual

Page 4

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

IMPORTANT: Make provisi-on for the auxii-
iaxy power to be always on (except for servic-
mg or prolonged shutdown) to ensure power
to the heaters.

A toggle switch (marked SW) in the control box
allows the control circuit to be manually discon­
nected when necessary. This switch does not
affect the crankcase heater, cooler heater cable
or convenience outlet.

3. Control Circuit Interlocks — A flow switch

should be installed in the chilled water line to
prevent the unit from running when water is not
circulating thru the cooler. This switch (no.
HR81LG005) is available as an accessory from
the Syracuse parts center, or equivalent can be
field purchased. Also, auxiliary contacts for the
chilled water pump starter should be installed in
the control circuit as additional protection
against unit operation when pump is not run­
ning. Both of these items should be electrically

interlocked in the control circuit, between
terminals [T] and [2 on TBS. See Fig. 3 for field
wiring.

UNIT CONTROL BOX

A-

SW

T8 I

CD [I]

TB4

REMOVE RED WIRE BETWEEN Q] AND

TBS

TB3

EQUIP GND

(Z)—1

TB2

L3 L2 LI

FIELD POWER SUPPLY

m

EQUIP

GND

L_

[T]

I

I

(AUX)'--

-|cWFsh'*~'ICWPsM

3 qp

LI

L2

CONTROL CIRCUIT

INTERLOCKS (ACCESS)

AUXILIARY
POWER SUPPLY

r+-

DISCONNECT PER NEC

LEGEND

CWFS — Chilled Water Flow Switch
CWPS — Chilled Water Pump Starter Auxiliary Contacts
SW

— On.Off Switch, Control Circuit

TB

— Terminal Board

___Field Control Wiring

Field

Power

Wiring

_ Factory Wiring

Fig. 3 — Field Wiring Connections

START-UP AND SERVICE

Initial Check

— Do not attempt to start the liquid

chiller, even momentarily, until the following steps

have been completed.

1. Check all auxiliary components such as chilled

liquid circulating pump, air handling equip­
ment, or other equipment to which the chiller
supplies liquid. Consult the manufacturer’s
instructions. Pump auxiliary contactor and

flow switch interlocks must be properly in­

stalled (see Fig. 3, Field Wiring Connections).

2. Check chilled water safety thermostat. (See

Safety Thermostat for adjustment.)

3. Backseat (open) compressor suction and dis­

charge shutoff valves. Close valves one turn to
allow pressure to reach test gages.

4. Open liquid line valve.

5. Fill chilled liquid circuit with clean water or

other noncorrosive fluids to be cooled. Bleed
all air out of high points of system.

6. Set temperature controller (see Multiple-Step

Controller).

7. Check tightness of all electrical connections.

8. Compressor oil should be visible in bull’s-eye

(see Oil Charge).

9. Be sure there are no refrigerant leaks (see Leak

Test and Dehydration).

10. Be sure unit is fully charged with refrigerant

(see Refrigerant Charge).

11. Electrical power source must agree with name­

plate rating.

12. Temperature sensor of fan cycling control must

be unobstructed (see Fan Cycling).

13. Crankcase heater must be firmly locked into

compressor crankcase. Be sure crankcase is
warm (heater should be on for 24 hours before
starting compressor).

14. Be sure compressor floats freely on the mount­

ing springs. See Compressor Mounting section

and Fig. 2 for installation of loose washers and
snubbers.

Leak Test and Dehydration

— All 30GA units are

shipped with complete operating charge of Refrig­
erant 22 (Table 1) and should be under sufficient
pressure to conduct leak test after installation. If
there is no system pressure, admit refrigerant until
a pressure is observed and then proceed to test for