beautypg.com

Water treatment, Power supply, Power wiring – Carrier 30GA User Manual

Page 3: Table 4 — electrical data

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

$»«je8ER Fl.AN«ED

WASHER

MEORRERE

SNUB8ER

. COMPRESSOR POOT

(SOCATJON SPRiNC

Fig. 2 — Compressor Mounting

Chilled Water and Drain Piping

— Facing the cooler

side of the unit, the return water connection is on
the left and the leaving water connection is on the
riglrt (see Fig. 1). The connections are oriented
vertically to minimize pressure losses and to facili­
tate field piping for roof-mounted installations. A
means of venting air from the high point of the

field-installed piping should be provided. After
field piping is complete, wrap all piping with elec­
tric heating tape and cover with suitable thickness
of closed-cell insulation. The power source for the
electric heating is the 115-volt (60-FIertz only) con­

venience outlet in the bottom of the cooler section,

at compressor end. The cooler drain connection is
at compressor end (see Fig. 1). Drain piping can be
installed directly thru hole provided in cooler
section base pan. Insulate this piping, similar to

the chilled water piping, for at least one foot
from cooler.

Water Treatment

— Consult local water authority

on characteristics of water in the area and add a
recommended inliibitor to the chilled water.

Power Supply

~ Electrical characteristics of avail­

able power supply must agree with unit nameplate
rating. Supply voltage must be within the limits
shown in Table 4.

IMPORTANT; Operation on improper supply

voltage or with excessive phase unbalance con-
.stitutes abuse and is not covered by Carrier
Warranty,

Power Wiring

— All power wiring must comply

with applicable local and national codes. Install a
field-supplied branch circuit disconnect switch per
NEC of a type that can be locked OFF or OPEN.
FIELD CONNECTIONS

1. Main Power — Bring wires from the disconnect

switch thru hole in bottom of unit control box

(Fig. 1) and connect to terminals LI, L2, L3 on

line side of terminal block TBl (see Fig. 3).

2. Auxiliary Power — Bring separate source power

(115-1-60) into unit as shown in Fig. 1 and Fig. 3.
This supplies power for control circuit, compres­
sor crankcase heater, cooler heater and conven­
ience outlet for miscellaneous auxiliary 115-volt
applications. Connect incoming wires to TB2 in
unit control box (LI toQ] and L2 to[2]). In the

auxiliary power supply, a field-supplied dis­
connect with 15-amp circuit protection must be

provided to take care of crankcase heater and
cooler heater cable.

In compliance with NEC Article 440-14, the dis­
connect must be located within sight of and
readily accessible from the unit.

Table 4 — Electrical Data

UNIT

COMPRESSOR

EACi-

V

d

U

s

Max

CCB

“ F

l

30GA

Mode I

Supp lied*

MCA

>"use

RLA

LRA

Fan

Min

Max

P

1 MTA

It

530

208/230

187

253

103

175

.........

76

......

^ 345

~6

S3

4.5

020

630

460

414

508

51

80

36

173

3

DO

1 9

130

575

518

632

41

60

28 6

120

3

1 40

1 6

530

208/230

187

253

145

225

100

446

6

.......

7(Г“

6.2

025

630

460

414

508

69

1 10

48

223

6

3 0

130

575

518

632

61,7

70

4d> .6

164

3

1 oT

2.4

530

208/230

187

253

168

275

\\o

506

6

83

6 2

030

630

460

414

508

72

110

ZiO

253

6

;

35

3 0

130

575

518

632

63 5

80

45

176

3

63

2 4

No.

2.3

4 6

1 9

1 6

6 6

3 0
2 4

6 6

3 0
2.4

CCB

-

FCB

-

FLA

-

LRA

-

MCA -

RLA for each motor winding is half the value shown

MTA shown is for eacli 3-pole section of the CB (each
motor winding)

Compressor Circuit Breaker

Fan Circuit Breaker (one for all fans)

Full Load Amps (fan motors)
Locked Rotor Amps

Minimum

Circuit

Amps

Complies

with

NEC,

Section

430-24

FCB

MTA

29

18
14

29

18
14

29

18
14

MTA — Must Trip Amps (factory-installed circuit breaker)
P — No of poles in CCB

RLA — Rated Load Amps (compressor)

*Units are suitable for use on electrical systems where voltage

supplied to the unit terminals is not below or above the min

and max limits shown

■fAdjacent to compressor compartment (non-cycling)

NOTE

Maximum

allowable

phase

unbalance

is

volts,

2%:

amps, 10%