background image

ON THE ROOF; MOUNT UNIT ON A LEVEL
PLATFORM OR FRAME: Proper precaution
must be taken for support of unit in roof design.
Elevate unit for proper clearance as described under

ground installation above. Plan roof design and
water drainage to prevent unit from setting in water.
Flash all roof openings to prevent leaks.

Roof mounted unit exposed to winds above 5 mph

may require protective wind baffles (field fabricated)

to achieve adequate defrost.

Step 3 — Make Piping Connections

— Heat

pumps may be connected to indoor sections using
Carrier accessory tubing package (Table 3) or field-
supplied tubing of refrigerant grade, correct size and

condition (Table 2). For requirements beyond
50 ft obtain information from local Carrier
distributor.

Table 2 — Installation Data (Fig. 1)

UNIT 38QF

018

024

030

036

042

048

060

OPER WT(lb)

160

163

181

189

209

265

298

DIMEN (ft-in.)

DIam (A)

Height (B)

Mtg Pad

(Diam X Thick)*

(C)

(D)

2-

53/32

2-2'V32 j

2

-

8

Y

32

[3-13/4

2-6 X 0-6

1-1

1-10/2

3-23/33

2-83/61 3-2’/e

3-3 X 0-6

1 -5%

2-7

REFRIG CONN (in.)

Suction (ODF)

Liquid (ODF)

34

3/s

REFRIG LINES (in.)

Suction (ODF)

Liquid (ODF)

% 1 1

Vaf

3/8

“■Mounting pad is fieid suppiied,

fMay use

Vs-'m.

accessory tubing package (slight capacity loss). See Tabie 3.

-> Table 3 — Accessories

PART NO.

DESCRIPTION

MODEL 38QF

99TZ90040106

99TZ90041106

Low-Voltage

Control

Honeywell

Thermostat

HH07AT171

and

Thermostat

Subbase HH93AZ173 — Automatic Changeover (Six 99TZ900401)

Low-Voltage Control —

Subbase HH93AZ175 ■

Honeywell Thermostat HH07AT171 and Thermostat

Manual Changeover (Six 99TZ900411)

All

38QB90002106

Service Sentry — Standard on 38QF060 (Six HN65CT004)

Twelve M x IVs-in. connection adapters

018-048

28VQ900011

030-060

38RQ90008106

HN61KL704

380890004106

38CQ900172

38RQ90009106

Bi-Flow Heat Pump Filter Drier — Ref KH45LD077 (Six 38RQ900081)

Supplemental Heat Relay ■
(Six 38RQ900001)

■ Required with 2 outdoor thermostats.

Outdoor Thermostat (Six 38QB900041)

Optimizer Control Outdoor Thermostat — Ref HH22AG110 (Six 38CQ900161)

Optimizer II Control Assembly — Use with HH22AG110 outdoor thermostat.

(Six 38RQ900091)

All

38QB90001106

Heat Pump Rack (Six)

018-042

38QF90000106

38QB90003106

Heat Pump Rack (Six)

Solid-State Time Guard

I

24 volt (Six 38QB900031)

048,060

38QF90001106t

Liquid Line Solenoid (Six 38QF900011)

All

HC95DE088*

Start Capacitor

018

HC95DD121*

Start Capacitor

024

HC95DD121“

Start Capacitor

030

HC95DE070*

Start Capacitor

036,042

HN61KA054*

Start Relay

018

HN61HB515*

Start Relay

024

HN61HB510*

Start Relay

030

HN61HB505*

Start Relay

036

HN61HB504*

Start Relay

042

38EB660002*

Wire Bundle for Start Capacitor and Relay

All

TUBING

PACKAGE

LENGTH

(ft)

TUBING

Liquid

OD

(in.)

Tube End OD

(in.

Suction^

OD

(in.)

Tube End OD

Evap

(in.)

Cond

(in.)

MODEL

38QF

38LS978151
38LS978201
38LS978251
38LS978301
38LS978351
38LS978401

38LS978501

15

20

25
30
35

40
50

Ve

Va
%

Ye
Ys
Ya
Ya

Ya
Ya
Ya
Ya
Ya
Ya

Ya**
Ya**
Ya**
Ya**
Ya**
Ya**
Ya**

%

3/4

3/4

34

3/4

3/4

Y

a

Y

a

3/4

3/4

Y

a

Y

a

3/4

3/4

All

■“Available thru Carrier Service Parts.
fStart capacitor and relay are required when using liquid line solenoid valve.
{Suction line is insulated and has 90° bend.

“■“Capacity reduction may occur when %-in. accessory tubing is used on 38QF042.