beautypg.com

Step 4 — make wiring connections, 4 m } h f c l, Do not use gas piping as an electrical ground – Carrier 48GH User Manual

Page 6

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

Table 2 — Electrical Data

MODEL

48

SERIES

V-PH

OPER

VOLTAGE

RANGE

TOTAL

AMPS

MAX BRANCH

CIRCUIT FUSE

SIZE (Amps)*

MCA

MIN

WIRE SIZE

(AWG)t

MAX WIRE

LENGTH

(ft)t

Min

Max

GL018

320

208-230-1

197

253

11 4

20

13.8

14

67

GL024

320

208-230-1

197

253

160

30

194

12

76

GH024

320

208-230-1

197

253

17 3

30

20 7

10

112

GL030

320/330

208-230-1

197

253

19 3

35

23 4

10

100

GH030

320/330

208-230-1

197

253

19.1

35

23 2

10

101

320/330

208-230-1

197

253

25 0

45

30.0

r 10

77

GL036

520/530

208/230-3

187

253

18 6

35

21 9

10

121

620/630

460-3

414

506

9 1

15

108

14

218

320/330

208-230-1

197

253

24.8

45

29 8

10

78

GH036

520/530

208/230-3

187

253

19 5

35

22.8

10

116

GL042

320

208-230-1

197

253

26.4

50

31 8

8

117

520

208/230-3

187

253

21 9

40

25.8

10

103

GH042

320

208-230-1

197

253

26 2

50

31 6

8

117

520

208/230-3

187

253

21.3

40

25.2

10

106

320

230-1

207

253

30 3

60

36 3

8

107

GL048

520

208/230-3

187

253

26 6

45

30 8

8

135

620

460-3

414

506

11.7

20

135

14

169

GH048

320

230-1

207

253

29 5

60

35.5

8

110

520

208/230-3

187

253

24 6

45

28 8

10

92

GL060

320/330

230-1

207

253

43.4

60

52 3

6

116

GH060

320/330

230-1

207

253

43 7

60

52 6

j 6

116

AWG —American Wire Gage

MCA —Minimum Circuit Ampacity

*Maximum Dual Element Size.
tUse only copper wire for field connections to unit. Wire size is

based on 60 C or 75 C copper conductor at 86 F (30 C) ambient
temperature and ampacity shown in table If other than 60 C or

75 C copper conductor is used, if ambient temperature is above
86F, or if voltage drop of the wire exceeds 2% of total rated
voltage of the unit, determine wire size from ampacity shown
and National Electrical Code (NEC). Wire lengths shown are

measured one way along wire path between unit and service
panel for minimum voltage drop.

Adhere to the following criteria when selecting,

sizing, and installing duct system:

1. Select and size ductwork, supply-air registers

and return-air grilles according to Carrier Sys­

tem Design Manual, Part 2. System airflow must

he within range of temperature rise and external

static pressure shown on unit AGA rating plate.

CAUTION; When duci-sj'stem fastening boks

are being drilled into side of Model

4 M } H f C L

instead of the unit ductnanges, use extreme care

to avoid puncturing coil or coil tubes.

2. Use a flexible transition between rigid ductwork

and unit to prevent transmission of vibration.

The transition may be screwed or bolted to duct

flanges. Use suitable gaskets to ensure a weather

and airtight seal.

3. Install an external, field-supplied air filter(s)

in return-air ductwork where it is easily accessible

for service. Recommended filter sizes are shown

in Table 1.

4. Size all ductwork for maximum required airflow

(either heating or cooling) for unit being in­

stalled. Avoid abrupt duct size increases or

decreases.

5. Adequately insulate and weatherproof all duct­

work located outdoors. Insulate ducts passing

thru an unconditioned space, and use a vapor

barrier in accordance with latest issue of

SMACNA and NESCA minimum installation

standards for heating and air conditioning

systems. Secure all ducts to building structure.

6. Flash, weatherproof and vibration-isolate all

openings in building structure in accordance

with local codes and good building practices.

Step 4 — Make Wiring Connections

WARNING: Umt cabinet must have an un~

intemipted. unbroken electrical ground to

minimize the possibility of personal injury'

if an electrical fault should occur. Ibis ground

may consist of electrical wire connected to unit

ground lug in control compartment, or conduit

approved for electrical ground when installed in

accordance with National Electrical Code and

local electrical codes.

Do not use gas piping

as an electrical ground.

A failure to follow this

warning could result in the installer being liable

for the personal injury' of others.

CAUI ION: A failure lo follow' these precau­

tions could result in damage to unit being

installed:

This manual is related to the following products: