beautypg.com

Carrier 48GH User Manual

Page 11

Attention! The text in this document has been recognized automatically. To view the original document, you can use the "Original mode".

background image

#

Proceed as follows to measure and change

manifold pressure:

a. Turn off gas to unit.

b. Remove pipe plug on gas valve outlet identified

as PRESS TAP, then connect manometer at

this point.

c. Turn on gas to unit and start heating section.

d. Measure and change manifold pressure with all

burners fired to obtain desired gas input.

e. Turn off gas to unit, remove manometer from

gas valve, and replace pipe plug.

ADJUSTING BURNER AIR SHUTTERS —

After burners have operated at full input for at least

10 minutes, adjust primary air to each burner to

ensure optimum heating performance. Make these

adjustments when unit is being installed and during

routine maintenance inspections at beginning of

each heating season. Be sure that each burner is

clean and free of deposits before adjusting primary

air.

The primary air to each burner is regulated by

burner air shutter on each burner. See Eig. 8 for

location of burner air shutter. With all burners

operating, adjust primary air to each burner as

follows:

1. Eoosen locking screw that secures air shutter

in place on burner, then partially close air shutter

until a slight yellow tip appears on top of burner

flames.

2. Open air shutter very slowly until yellow tip just

disappears, then secure air shutter in place with

locking screw.

3. Repeat steps 1 and 2 for each burner.

After air shutter adjustments have been com­

pleted, observe that flames on each burner are light

blue and “soft” in appearance, and that flames are

same height along the entire length of each burner.

See Fig. 8.

AIR

SHUTTER

Fig. 8 — Burner Flames

BLOWER HEAT-RELAY OPERATION —

Heating relay (see Fig. 6 and unit wiring diagram) is

located in control box and adjusts to permit either

longer or shorter OFF cycles. The ON cycle auto­

matically adjusts as OFF cycle changes. Adjusting

lever on relay is factory-set at center position to

provide optimum performance for most installa­

tions. On unusual installations, or where line voltage

is considerably above or below rated voltage, length

of time blower remains on may require increasing or

decreasing. To increase blower operation time,

move adjusting lever toward right-hand position.

In this position, control makes contact sooner and

takes maximum time to break contact. To decrease

blower operation time, move lever toward left-

hand position.

AIRFLOW AND TEMPERATURE RISE —

Temperature rise is temperature difference between

air in return duct and air in discharge duct at unit.

Heating section of each size of unit is designed and

approved for heating operation within temperature

rise range stamped on unit rating plate.

Table 4 shows the approved temperature rise

range for each unit and air delivery (cfm) at various

temperature rises for both AGA-certified gas

input ratings. Heating operation airflow must

produce a temperature rise that falls within

approved range.

Table 4 — Air Delivery (Cfm) at Indicated Temperature

Rise and Rated Heating Input

MODEL

48

HEATING

INPUT

(Btuh)

TEMPERATURE RISE (F)

35

37 5

40

42 5

45

47,5

50

52 5

55

57 5

60

62 5

65

67 5

70

72 5

75

GL018,024,

40,000*

794

741

694

654

617

585

556

529

505

483

463

444

427

412

397

383

370

030

50,000

1032

963

903

850

802

760

722

688

657

628

602

578

556

535

516

498

481

GH024.030

60,000* 1190 1111 1042

980

926

877

833

794

758

725

694

667

641

617

595

575

556

GL036.O42

75,000

1548 1444 1354 1275 1204 1140 1083

1032

985

942

903

867

833

802

774

747

722

GH042

80,000*

1587 1481 1389 1307 1235 1170 nil

1058 1010

966

926

889

855

823

794

766

741

GL048

100,000

2063 1926 1806 1699 1605 1520 1444

1376 1313 1256 1204 1156 1111 1070 1032

996

963

GH036.048

100,000* 1984 1852 1736 1634 1543 1462 1389

1323 1263 1208 1157 1111 1068 1029

992

958

926

GL06O

1 25,000

2579 2407 2257 2124 2006 1901 1806

1720 1641 1570 1505 1444 1389 1337 1290 1245 1204

GH060

120,000* 2381 2222 2083 1961 1852 1754 1667

1587 1515 1449 1389 1333 1282 1235 1190 1149 1111

150,000

3095 2889 2708 2549 2407 2281 2167

2063 1970 1884 1806 1733 1667 1605 1548 1494 1444

“These inputs are the minimum rated inputs using factory-installed burner

orifices Higher inputs shown for each size are the maximum rated inputs

using field-installed, optional burner orifices that are indicated on unit

rating plate

NOTE: Models 48GL018,024,036; 48GH024,030 have an approved tem­

perature rise range of 35 to 75 F All other units have an approved tempera­
ture rise range of 45 to 75 F

11

This manual is related to the following products: