beautypg.com

1 power supply requirements, 2 terminal specification, 3 generator voltage / frequency sensing – Winco DSE3000 Series User Manual

Page 7

background image

DSE Model 3000 Series Control & Instrumentation System Operators Manual

Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM

7

3.1 POWER SUPPLY REQUIREMENTS


Minimum supply voltage

8V continuous

Cranking dropouts

Able to survive 0V for 50mS providing the supply was at least 10V
before the dropout and recovers to 5V afterwards.

Maximum supply voltage

35V continuous (60V protection)

Reverse polarity protection

-35V continuous

Maximum operating current

30mA at 24V
35mA at 12V

Nominal standby current

23mA at 24V
18mA at 12V

Maximum Power Save mode current*

3.5mA at 24V
3.5mA at 12V

NOTE:- * Power Save mode is a configurable item. If enabled, the module switches to Power Save

mode when in STOP mode for more than 1 minute (60 seconds)


Plant supply instrumentation display

Range

0V-60V DC (note Maximum continuous operating voltage of 35V DC)

Resolution

0.1V

Accuracy

1% full scale

3.2 TERMINAL SPECIFICATION


Connection type

Screw terminal, rising clamp, no internal spring

Min cable size

0.5mm² (AWG 24)

Max cable size

2.5mm² (AWG 10)

3.3 GENERATOR VOLTAGE / FREQUENCY SENSING


Measurement type

True RMS conversion

Sample Rate

5KHz or better

Harmonics

Up to 11

th

or better

Input Impedance

300K

ph-N

Phase to Neutral

15V to 333V AC (max)

Phase to Phase

25V to 576V AC (max)

Common mode offset
from Earth

100V AC (max)

Resolution

1V AC phase to neutral
2V AC phase to phase

Accuracy

±1% of full scale phase to neutral
±2% of full scale phase to phase

Minimum frequency

3.5Hz

Maximum frequency

75.0Hz

Frequency resolution

0.1Hz

Frequency accuracy

±0.2Hz