Winco DSE3000 Series User Manual
Page 21
DSE Model 3000 Series Control & Instrumentation System Operators Manual
Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM
21
6.1.3 ENGINE RUNNING
Once the engine is running and all starting timers have expired, the animated
icon is displayed
.
DSE3110 - The generator will be placed on load if configured to do so.
NOTE:-The load transfer signal remains inactive until the Oil Pressure has risen. This prevents
excessive wear on the engine.
If all start requests are removed, the stopping sequence will begin.
6.1.4 STOPPING SEQUENCE
The return delay timer operates to ensure that the starting request has been permanently removed and isn’t just a
short term removal. Should another start request be made during the cooling down period, the set will return on
load.
If there are no starting requests at the end of the return delay timer, the load is removed from the generator to the
mains supply and the cooling timer is initiated.
The cooling timer allows the set to run off load and cool sufficiently before being stopped. This is particularly
important where turbo chargers are fitted to the engine.
After the cooling timer has expired, the set is stopped.