beautypg.com

Winco DSE3000 Series User Manual

Page 19

background image

DSE Model 3000 Series Control & Instrumentation System Operators Manual

Part No. 057-086 3000 Series OPERATING MANUAL ISSUE 4 03/12/2009 ADM

19

5.4 CONTROLS

Stop / Reset
This button places the module into its Stop/Reset mode. This will clear any alarm conditions for
which the triggering criteria have been removed. If the engine is running and the module is in Stop
mode, the module will automatically instruct the changeover device to unload the generator (‘Close
Generator
becomes inactive (if used))
. The fuel supply de-energises and the engine comes to a
standstill. Should a remote start signal be present while operating in this mode, a remote start will
not occur.

Auto
This button places the module into its ‘Automatic’ mode. This mode allows the module to control the
function of the generator automatically. The module will monitor the remote start input and once a
start request is made, the set will be automatically started and placed on load.
Upon removal of the starting signal, the module will automatically transfer the load from the generator
and shut the set down observing the stop delay timer and cooling timer as necessary. The module will
then await the next start event. For further details, please see the more detailed description of ‘Auto
operation’ elsewhere in this manual.

Start
Pressing this button in auto mode will start the engine and run off load.
Pressing this button in STOP/RESET mode will turn on the CAN engine ECU (when correctly
configured and fitted to a compatible engine ECU)

Page
Pressing this button scrolls the display to show the various instruments.