4.2 TERMINAL DESCRIPTION
4.2.1 DC SUPPLY, FUEL AND START OUTPUTS
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
1
DC Plant Supply Input
(Negative)
2.5mm²
AWG 13
2
DC Plant Supply Input
(Positive)
2.5 mm²
AWG 13
(Recommended Maximum Fuse 15A anti-surge)
Supplies the module (2A anti-surge requirement) and all
output relays
3
Output A (FUEL)
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
4
Output B (START)
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
5
Output C
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
6
Output D
1.0mm²
AWG 18
Plant Supply Positive from terminal 2. 3 Amp rated.
7
Charge fail / excite
2.5mm²
AWG 13
Do not connect to ground (battery negative).
If charge alternator is not fitted, leave this terminal
disconnected.
4.2.2 GENERATOR VOLTAGE SENSING AND DIGITAL INPUTS
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
8
Generator Neutral (N) input
1.0mm²
AWG 18
Connect to generator Neutral terminal (AC)
9
Generator L1 (U) voltage
monitoring
1.0mm²
AWG 18
Connect to generator L1 (U) output (AC)
(Recommend 2A fuse)
4.2.3 MAGNETIC PICKUP AND DIGITAL INPUTS (MODEL 3110-XX-01)
Model 3110-xx-01 (Magnetic pickup enabled module)
NOTE:- CAN interface is not fitted to the 3110-xx-01 module
PIN
No
DESCRIPTION
CABLE
SIZE
NOTES
10
Magnetic pickup Positive
0.5mm²
AWG 20
Connect to Magnetic Pickup device
11
Magnetic pickup Negative
0.5mm²
AWG 20
Connect to Magnetic Pickup device
12
Configurable digital input A
0.5mm²
AWG 20
Switch to negative
13
Configurable digital input B
0.5mm²
AWG 20
Switch to negative
14
Configurable digital input C
0.5mm²
AWG 20
Switch to negative
15
Configurable digital input D
0.5mm²
AWG 20
Switch to negative
16
Configurable digital input E
0.5mm²
AWG 20
Switch to negative
17
Configurable digital input F
0.5mm²
AWG 20
Switch to negative
NOTE:- Screened cable must be used for connecting the Magnetic Pickup, ensuring that the screen is
earthed at one end ONLY.