beautypg.com

Winco ULPSS90/D WITH DSE 7310 CONTROL (2014) User Manual

Page 7

background image

7

48-00

60706-51

FUEL INSTALLATION

The fuel supply should be as close as possible to the engine.

This will reduce the installation cost of fuel runs. The information

in this manual is offered to assist you in providing the proper fuel

for your engine. However, this information is only provided to

inform you of the engine’s requirements and assist in making you

aware of the decisions you must make. In no case should the

instructions or information provided be interpreted to conflict with

any local, state or national codes. If in doubt, always consult

your local fire marshal or gas supplier.

****************

***** WARNING *****

****************

FIRE HAZARD - All fuel runs should be installed by a licensed

fuel supplier.

Connect the fuel supply to the inlet of the fuel solenoid (see

table for recommended line size). The pressure at the demand

regulator must be four to six ounces per square inch or 7 to 11

inches W.C. (Water column) on vapor withdrawal units. On units

equipped with liquid withdrawal fuel systems full tank pressure

is plumbed to the fuellock strainer mounted on the generator

rails. The fuel converter mounted on the unit will handle both

vaporization of the fuel and pressure reduction.

INSTALLING THE FUEL LINE

** NOTICE **

The engine generator sets are properly adjusted before they

leave the factory for a specific fuel, either NG (natural gas), LP

(liquid propane vapor) or LPG (liquid withdrawal propane). This

fuel type is noted in your model number. If it becomes necessary

to change the fuel type in the field see information on page 16.

Line Size (vapor system)

Unit location will determine the size of fuel line that is required

to supply the engine with a constant fuel pressure. Refer

to the tables below for fuel line size, fuel consumption and

recommended tank size. For distances of 5 feet and over, a

two regulator fuel system is recommended. This is accomplished

by installing a primary regulator at the tank which will reduce the

tank pressure down to 10 to 15 lbs. A secondary regulator is

installed to further reduce the fuel pressure to the required six (6)

oz operating pressure. This secondary regulator must be at least

10 feet from the engine generator set. Any closer installation

will require a larger line be installed to provide a fuel reservoir.

If this is not done, the demand regulator on the unit and the

pressure regulator in the fuel line will interfere with each other.

When this two (2) stage regulator system is used, a fuel line size

of 3/4 to 1 inch is generally adequate for distances up to 300 feet

from the primary to the secondary regulator. (Consult your local

fuel supplier for your exact requirements). The appropriate line

size from the table below is then installed from the secondary

regulator to the generator set.

****************

***** WARNING *****

****************

PERSONAL DANGER - Do not use galvanized pipe in fuel line

runs. The galvanized coating can become eroded and flake off,

causing possible obstructions in the regulator or fuel valve. The

results could range from inoperative engine start to hazardous

fuel leaks.

Size of pipe normally required for generators operating on NG/

LP:

UP TO

5 FEET*

OVER

5 FEET

PSS60

1.5” pipe

NOT

RECOMMENDED**

PSS90

1.5” pipe NOT

RECOMMENDED**

* Allow an additional 3 feet for each standard elbow.

Do not use ‘street ells’ (restrictive).

** USE THE TWO REGULATOR SYSTEM SHOWN BELOW.

**** CAUTION ****

EQUIPMENT DAMAGE - Be careful when sealing gas line joints.

Excessive sealing compound can be drawn into the solenoid,

regulator or carburetor causing an engine malfunction.

FUEL PRESSURE (vapor system)

Correct fuel pressure cannot be stressed enough. The most

common cause for inoperative systems is an inadequate or

incorrect fuel pressure. Power and performance of the engine

is in direct relation to the correctness of the fuel system. Shown

below is a diagram of a typical L.P. or N.G. installation.

Reference numbers 1 through 3 in the diagrams below are

system parts supplied by customer.

Reference number 4 is the engine generator set.

Below is a table of the fuel pressure reading at each reference in

the system.

Fuel Pressure Table

This manual is related to the following products: