beautypg.com

Troubleshooting tables – Winco ULPSS90/D WITH DSE 7310 CONTROL (2014) User Manual

Page 15

background image

15

48-00

60706-51

4. During manual operation the load will not normally be applied

to the generator. But caution must be used, if the line power

should fail or be turned off to the transfer switch during manual

operation the load may be applied to the generator.

With the engine running smoothly check the no load voltage

and frequency on the digital display. The voltage should be

08/40/480 AC depending on which model you have and a

frequency of 59.5 To 60.5 hertz (Hz).

If you have the proper voltage at the generator the next step is

to check the voltage at the generator terminals in the Automatic

Transfer Switch. The voltage between the G1 and the G3

terminals should be the same as it was on the generator front

panel. The voltage should also be checked between the hot

terminals (G1 and G3) and the G-N to be certain of a balanced

voltage output and a solid neutral connection. The voltage

between G1 and G-N should be about 10 volts AC (77 on 480

units). The same approximate voltage should be found between

terminals G3 and G-N (120 volts AC).

On three phase panels the G voltage level should also be

checked. ON 240 VOLT (DELTA) SYSTEMS BE SURE YOU

KNOW WHERE THE HIGH VOLTAGE “WILD” LEG IS. IT MUST

BE IN THE SAME LOCATION ON THE LINE SIDE AS IT IS ON

THE GENERATOR SIDE. (i.e. if it’s on L-3 on the line side it

must be on G-3 on the generator side.

** Notice **

If for any reason during the check out procedure the voltage and

frequency are not correct, depress the STOP/RESET button and

correct the trouble before proceeding.

5. Stopping – There are two ways to stop the unit when it is in

the manual mode. Pressing the STOP/RESET button will stop

the unit immediately. Pressing the AUTO mode button will stop

the unit but only after the cool down timers have timed out and

there is no remote start signal being sent to the unit.

AUTO MODE

To activate the automatic start mode you will just need to

depress the AUTO button, the LED indicator beside the button

confirms that the unit is in automatic start mode.

To test the automatic start Transfer Switches follow the

instruction in the operator’s manual you received with your

transfer switch. If you get a fault light during the initial start up

or prior to start up it is most likely a false warning light. Simply

reset the ATS and start over.

Once you have completed testing of the ATS, be sure you

ALWAYS leave the system in standby mode unless servicing the

unit. For standby operation, press the AUTO button on the front

of the engine control. The green light should light up next the

AUTO button.

SETTING THE EXERCISER CIRCUIT

For all ATS see the instruction manual shipped with the ATS for

instruction on setting the exercise circuit in your ATS

TROUBLESHOOTING TABLES

UNIT WILL NOT CRANK WHEN THE POWER FAILS

1. Digital Genset Controller not in “AUTO”.

. Transfer control switch not in “AUTOMATIC”

position.

3. Incorrect wiring between transfer switch and

generator.

4. Blown fuses on Digital Genset Controller.

5. Defective Digital Genset Controller.

6. Loose or dirty battery terminals.

7. Defective auto start controller in the

transfer switch.

8. Defective starter.

9. Defective start solenoid.

ENGINE WILL NOT CRANK WITH GENERATOR

RUN PUSH-BUTTON DEPRESSED

1. Battery dead.

. Blown fuses Digital Genset Controller.

3. Defective Digital Genset Controller.

4. Loose or dirty battery terminals.

5. Defective starter.

6. Defective start solenoid.

7. Locked up engine genset.

ENGINE CRANKS BUT WILL NOT START

1. Improper fuel pressure being delivered to

unit.

. Fuel supply shut off.

3. Fuel tank empty.

4. Defective spark plug.

5. Defective engine ignition module.

6. Dirty air cleaner filter.

7. Defective fuel solenoid valve.

8. Low battery.

9. Defective fuel regulator.

10. Defective ECU on the engine.

ENGINE STARTS AND THEN STOPS AND ALARM

LIGHT COMES ON

1. Engine is low on oil.

. Engine has high water temperature.

3. Engine has overspeed.

4. Engine has gone into overcrank.

5. No output from engine alternator to engage

stop crank circuit.

6. Generator is not aoperating at the correct speed.

7. Defective ECU on the engine

ENGINE WILL NOT COME UP TO SPEED AFTER IT STARTS

1. Insufficient fuel volume getting to the unit.

a. Too small of fuel line.

b. Fuel pressure too low/high.

. Defective ECU on the engine.

3. Governor is defective.

4. AC short in generator components.

This manual is related to the following products: