48-00
60706-51
ATS PANEL WILL NOT TRANSFER TO EMERGENCY SUPPLY
(GENERATOR)
1. No AC generator output from generator.
. Defective transfer switch controller.
3. Incorrect voltage or frequency from the generator.
4. Wiring error between generator and transfer
switch.
5. Defective mechanically switching solenoid in
Automatic Transfer Switch.
6. Improper phase rotating.
7. Main line breaker on generator open/defective.
ATS PANEL WILL NOT RETRANSFER TO NORMAL POWER
1. Proper normal line power not available at line
terminals in ATS panel.
. Defective transfer switch controller.
3. Defective mechanically switching solenoid in
Automatic Transfer Switch.
4. Retransfer delay still timing out.
NO AC OUTPUT FROM GENERATOR
1. Defective diode.
. Defective voltage regulator.
3. Defective rotor.
4. Defective stator.
5. Defective exciter rotor.
6. Defective exciter stator.
7. AC short in the output leads.
8. Defective field circuit breaker.
CHANGING THE FUEL TYPE
**** CAUTION ****
EQUIPMENT DAMAGE - Do not make any fuel adjustments
or governor adjustments until all pressure readings are in
compliance with specification. See fuel pressure charts (tables
1, 2, and 3).
These engine/generator sets are very easy to convert between
LP or NG. As the engine timing is controlled by the ECU on the
engine you only need to tell it what fuel you want to operate on.
A small rocker switch has been provide on the underside of the
engine control cabinet (see ref L on Page 13) for this purpose.
Opening the rocker switch will tell the ECU mounted on the
engine that you are operating on NG Fuel. Closing the rocker
switch will tell the ECU that the fuel being supplied is LP. The
Advance Power Controller has an idicator light for LP. When this
light is lite the engine is set-up for LP, when the LP light is out the
engine is set up for NG. The ECU will then reprogram the engine
to operate on the proper fuel.
GENERATOR SPECIFICATIONS
PSS60-3
Stanford Newage Model# UCI4F1J
06 Winding (Single phase 4 lead generator)
Winco Part Number
35198-41
Voltage Regulator
AS440
Rotor Resistance
0.83 ohm
Stator Resistance
0.01 ohm
Excitor Stator Resistance 0.0 ohm
Excitor Rotor Resistance 0.156 ohm
PSS60-4/-17/18
Stanford Newage Model# UCI4F1L
311 Winding (Three phase 12 lead reconnectable)
Winco Part Number
35198-4
Voltage Regulator
AS440
Rotor Resistance
0.83 ohm
Stator Resistance
0.033 ohm
Excitor Stator Resistance 0.0 ohm
Excitor Rotor Resistance 0.156 ohm
PSS90-3
Stanford Newage Model# UCI74C1J
06 Winding (Single phase 4 lead generator)
Winco Part Number
35013-1
Voltage Regulator
AS440
Rotor Resistance
1.1 ohm
Stator Resistance
0.011 ohm
Excitor Stator Resistance 0.0 ohm
Excitor Rotor Resistance 0.18 ohm
PSS90-4/-17/18
Stanford Newage Model# UCI74C1L
311 Winding (Three phase 12 lead reconnectable)
Winco Part Number
35013-
Voltage Regulator
AS440
Rotor Resistance
1.1 ohm
Stator Resistance
0.03 ohm
Excitor Stator Resistance 0.0 ohm
Excitor Rotor Resistance 0.18 ohm
GENERATOR REPLACEMENT PARTS
The following list of replacemnt parts apply to all four generator
models listed for these generators:
Description
Stanford Part #
Automaic Voltage Regulator
E000-4403
Winco Part #
350818-
Bearing UCI4
051-0103
UCI7
051-01049
Rectifier Service Kit
RSK-2001
Comprises of
6 Diodes with Surge Suppressor