Specifications lp rating, Ng rating – Winco ULPSS90/D WITH DSE 7310 CONTROL (2014) User Manual
Page 5
5
48-00
60706-51
FUNCTIONS
DSE 7310 Series Control Modules perform the following
protection and metering functions:
Generator Protection and Metering
Generator protection includes over voltage, under voltage,
under frequency, over frequency and overload protection. Each
generator protection function has an adjustable pickup and time
delay setting. Metered generator parameters include voltage,
current, real power (watts), power factor (PF)
Engine Protection and Metering
Engine protection features include oil pressure and coolant
temperature monitoring, over crank protection, ECU specific
protection elements, and diagnostic reporting.
Metered engine parameters include, oil pressure, coolant
temperature, battery voltage, speed, engine load, coolant level
(from ECU), ECU specific parameters, and run-time statistics.
** NOTICE **
These units will automatically transfer if a power outage occurs
while running in an exercise mode.
SPECIFICATIONS
LP RATING
MODEL
WATTS VOLTS
AMP
HZ
PH RPM
PSS60-3
56,000 10/40
33*
60
1
1800
PSS60-4
60,000 10/08
08**
60
3
1800
PSS60-17 60,000 10/40
180**
60
3
1800
PSS60-18 60,000 77/480
90**
60
3
1800
PSS90-3
80,000 10/40
333*
60
1
1800
PSS90-4
80,000 10/08
78**
60
3
1800
PSS90-17 80,000 10/40
40**
60
3
1800
PSS90-18 80,000 77/480
10**
60
3
1800
NG RATING
MODEL
WATTS VOLTS
AMP
HZ
PH RPM
PSS60-3
55,000 10/40
9*
60
1
1800
PSS60-4
58,000 10/08
01**
60
3
1800
PSS60-17 58,000 10/40
174**
60
3
1800
PSS60-18 58,000 77/480
87**
60
3
1800
PSS90-3
90,000 10/40
375*
60
1
1800
PSS90-4
90,000 10/08
31**
60
3
1800
PSS90-17 90,000 10/40
70**
60
3
1800
PSS90-18 90,000 77/480
135**
60
3
1800
*Unity Power Factor - Derate 3.5% per 1000 feet elevation above
sea level.
**Power Factor .8 - Derate 3.5% per 1000 feet elevation above
sea level.
FUEL CONSUMPTION
NG
LP VAPOR
(1,000 BTU/CU FT) (2,520 BTU/CU FT)
MODEL CF/
HR
BTU/HR
#/HR GAL/
HR
CF/
HR
BTU/HR
PSS60
799
799,000
39.4
9.9
334 850,964
PSS90
130 1,30,000 5.6
1.4
446 1,149,00
L.P. TANK SIZING
Minimum required L.P. Tank size for L.P. Vapor withdrawal
operating at various outside temperatures given in degrees
Fahrenheit (Celsius)
TANK TEMPERATURE
MODEL 60 F(16 C) 30 F(0 C) 0 F(-18 C) -20 F(-29 C)
PSS60
500 Gal
1000 Gal 000 Gal*
5000 Gal*
PSS90
500 Gal
1000 Gal 000 Gal*
5000 Gal*
*Recommend liquid withdrawal at these temperatures.
ENGINE SPECIFICATIONS:
** NOTICE **
Regarding Engines - This manual covers the generator portion
of these units. See the separate engine instruction manual
for engine-related problems, detailed engine information and
engine warranty. Refer to engine operating and maintenance
instructions
** CAUTION **
EQUIPMENT DAMAGE - Be sure to check the engine oil level
frequently as specified in the engine manual.
The engine manufacturer has established an excellent worldwide
engine service organization; engine service is available from a
nearby authorized dealer or distributor. Go to the WINCO web
site for a list of engine dealers. (http://www.wincogen.com/
Engine_Support/ )
The rated power of each engine-generator is limited by the
temperature, altitude and all other ambient conditions specified
by the engine manufacturer. Engine power will decrease 3-1/%
for each 1000 ft. above sea level, and will decrease an additional
1% for each 10
o
Fahrenheit above 60
o
Fahrenheit. Units should
not be operated in ambient temperature greater than 104
o
F.