6 | PIR Ready VTR7300 Series-Installation Guide
Network ready
All Viconics VTR7300 series Terminal Equipment Controllers are designed for
stand-alone operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:
o VCM7000V5000W, Terminal Equipment Controller wireless
communication adapter
o VCM7300T5000B, Terminal Equipment Controller
BACnet™ MS-TP
communication adapter
T
ERMINAL
,
I
DENTIFICATION AND
F
UNCTION
TERMINAL
IDENTIFICATION
ALL VTR73XXA5X00(X)
TERMINAL EQUIPMENT CONTROLLER
Terminal 3
Tx
– Rx Communication
Terminal 4
Power Hot 7.0 VDC
Terminal 5
Power Common
Terminal 13
BI 1 ( Configurable )
Terminal 14
Scom
Terminal 15
BI 2 ( Configurable )
C
OMMUNICATION WIRING TO
VC3
XXX
X
R
ELAY
P
ACK
Only ONE VC3xxxX Relay Pack with remote monitoring inputs can be used under a single
VTR73xxA Controller. All other slave units must be VC3xxxX Relay Pack(s) WITHOUT
remote inputs. A maximum of 10 VC3xxxX Relay Packs can be used for a single
VTR73xxA Terminal Equipment Controller.