beautypg.com

Network ready, Terminal, identification and function, Communication wiring to vc3xxxx relay pack – Viconics VTR7300 Installation Manual User Manual

Page 6

background image

6 | PIR Ready VTR7300 Series-Installation Guide

Network ready

All Viconics VTR7300 series Terminal Equipment Controllers are designed for
stand-alone operation.

They can be fully integrated into your choice of automation systems using the
available communication adapter options.

If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:

o VCM7000V5000W, Terminal Equipment Controller wireless

communication adapter

o VCM7300T5000B, Terminal Equipment Controller

BACnet™ MS-TP

communication adapter

T

ERMINAL

,

I

DENTIFICATION AND

F

UNCTION

TERMINAL

IDENTIFICATION

ALL VTR73XXA5X00(X)

TERMINAL EQUIPMENT CONTROLLER

Terminal 3

Tx

– Rx Communication

Terminal 4

Power Hot 7.0 VDC

Terminal 5

Power Common

Terminal 13

BI 1 ( Configurable )

Terminal 14

Scom

Terminal 15

BI 2 ( Configurable )

C

OMMUNICATION WIRING TO

VC3

XXX

X

R

ELAY

P

ACK

Only ONE VC3xxxX Relay Pack with remote monitoring inputs can be used under a single
VTR73xxA Controller. All other slave units must be VC3xxxX Relay Pack(s) WITHOUT
remote inputs. A maximum of 10 VC3xxxX Relay Packs can be used for a single
VTR73xxA Terminal Equipment Controller.