Viconics VTR7300 Installation Manual User Manual
Page 17
17 | PIR Ready VTR7300 Series-Installation Guide
RUI 1
Cont’d
Contact opened = No alarm
Contact closed = Alarm displayed
(Service): A backlit flashing Service alarm will be displayed on
the Terminal Equipment Controller LCD screen when the input
is energized. It can be tied in to the AC unit control card, which
provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
RBI 2
Remote Binary input no.2
configuration
Default value = None
(None): No function will be associated with the input. Input can
be used for remote network monitoring.
(Filter): a backlit flashing Filter alarm will be displayed on the
Terminal Equipment Controller LCD screen when the input is
energized. It can be tied to a differential pressure switch that
monitor filters.
Contact opened = No alarm
Contact closed = Alarm displayed
(Service): a backlit flashing Service alarm will be displayed on
the Terminal Equipment Controller LCD screen when the input
is energized. It can be tied in to the AC unit control card, which
provides an alarm in case of malfunction.
Contact opened = No alarm
Contact closed = Alarm displayed
MenuScro
Menu scroll
Default value = On =
Scroll active
Removes the scrolling display and displays the room
temperature/humidity to the user. With this option enabled, no
mode, schedule and outdoor temperature status is given.
On = Scroll active
Off = Scroll not active
AutoMode
Enables Auto menu for
Mode button
Default value = On
Enables Auto function for the mode button
For sequences 2, 4 & 5 only
On = Auto active (Off-Cool-Heat-Auto)
Off = auto not active (Off-Cool-Heat)
C or F
Sets scale of the Terminal
Equipment Controller
Default value = °F
°F for Fahrenheit scale
°C for Celsius scale
On hotel models, this sets the default value when the Terminal
Equipment Controller powers up