User interface, Local keypad interface – Viconics VTR7300 Installation Manual User Manual
Page 10
![background image](/manuals/715546/10/background.png)
10 | PIR Ready VTR7300 Series-Installation Guide
U
SER
I
NTERFACE
Unoccupied mode override
An Override can be made on commercial models during an unoccupied period. If the
Override option is enabled in the lockout configuration, pressing the middle override
button will resume occupied setpoints for a time specified by the parameter
“ToccTime”.
Local keypad interface
Any setpoint change can be permanent or temporary based on configuration
parameter (Setpoint Type)
Any setpoint written through the network, will be permanent and cancel any
active temporary setpoints
Lockouts of access to certain functions is made with configuration parameter
(lockout)
Is used to toggle between the different system modes available as per
sequence and menu selected.
Repetitively pressing the button will toggle between all the available modes.
Available menus are dependent on selected sequence of operation.
Is used to toggle between the different fan modes available as per the
sequence and menu selected
Repetitively pressing the button will toggle between all the available modes
Available menus are dependent on selected sequence of operation and menu
selected for Fan
Hotel and lodging applications. Toggles the local user temperature scale
between
°F
and
°C
Commercial and institutional applications. Set a local unoccupied timed
override to occupied mode
In cooling mode only the cooling setpoint is displayed,
In heating mode only the heating setpoint is displayed
In auto mode, (See below)
In cooling mode only the cooling setpoint is displayed,
In heating mode only the heating setpoint is displayed
In auto mode, (See below)