15 | PIR Ready VTR7300 Series-Installation Guide

Get From
Terminal Equipment
Controller Get From
another device
configuration utility
Default value = 0
Range is: 0 to 254

Conditional parameter to Wireless models
VTR73xxX5x00W
Entering a MAC address enables an automatic routine that
automatically fetches all the required configuration properties of
the current device from another already configured device an
copies the same required configured property values.
If a value other than the default value of 255 is entered, user
will then be prompted to exit the Configuration Menu thus
leaving all other parameter configuration to be copied from the
referenced controller MAC address.

Ex.: If you are currently configuring MAC12 and the settings
matches exactly the settings of ZN MAC5, then enter 5 as the
current parameter value.

If the process is successful and all required configuration
properties have been copied, the value will revert back to
255

If the process is NOT successful and all required
configuration properties have NOT been copied ( either the
reference device is NOT the same model number or is
offline or does not exists ) the value will revert back to 254
to indicate the failure of the process

Leaving the Get From parameter to 255 means that every
configuration parameters will be set manually.

BI 1
Binary input no.1
configuration
Default value = None

(None): No function will be associated with the input. Input can
be used for remote network monitoring.

(Rem NSB): remote NSB timer clock input. The scheduling will
now be set as per the binary input. It provides low cost setback
operation via a dry contact

Contact opened = Occupied

Contact closed = Unoccupied

(Motion NO) or (Motion NC): Advanced PIR occupancy
functions using a Normally Open (NO) or Normally Closed (NC)
remote PIR motion sensor. Occupancy mode is now set as per
applied PIR function and configuration. Application information
and examples are available in document: APP-PIR-Guide-Exx.
This document will provide the installers and system designers
with detailed examples on applications, parameter configuration
information, sequence of operation, troubleshooting and
diagnostic help required for the proper usage of the PIR
accessory covers

(Window) EMS: Forces the system to disable any current
heating or cooling action by the Terminal Equipment Controller.
The mode stays the same and the current setpoints are the
same Occupied setpoints. Only the outputs are disabled. There
is a Door/Window alarm displayed on the Terminal Equipment
Controller to indicate to the local tenant that the door/window
needs to be closed for cooling or heating to resume.

Contact opened = Window Opened

Contact closed = Window Closed