Viconics VTR7300 Installation Manual User Manual
Page 24
![background image](/manuals/715546/24/background.png)
24 | PIR Ready VTR7300 Series-Installation Guide
S
PECIFICATIONS
Terminal Equipment Controller power
requirements:
Operating conditions:
Storage conditions:
Temperature sensor:
Temperate sensor resolution:
Temperature control accuracy:
Humidity sensor and calibration:
Humidity sensor precision:
Humidity sensor stability:
Dehumidification setpoint range:
Occ, Stand-By and Unocc cooling setpoint range:
Occ, Stand-By and Unocc heating setpoint range:
Room and outdoor air temperature display range:
Proportional band for room temperature control:
Binary inputs:
Wire gauge:
Approximate shipping weight:
Agency Approvals all models:
Agency Approvals all models:
Agency Approvals Wireless models:
7.0 VDC +/- 10% 2.4 watts minimum
0 °C to 50 °C ( 32 °F to 122 °F )
0% to 95% R.H. non-condensing
-30 °C to 50 °C ( -22 °F to 122 °F )
0% to 95% R.H. non-condensing
Local 10 K NTC thermistor
± 0.1 °C ( ± 0.2 °F )
± 0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F )
typical calibrated
Single point calibrated bulk polymer
type sensor
Reading range from 10-90 % R.H.
non-condensing
10 to 20% precision is 10%
20% to 80% precision is 5%
80% to 90% precision is 10%
Less than 1.0 % yearly (typical drift)
30% to 95% R.H.
12.0 to 37.5 °C ( 54 to 100 °F )
4.5 °C to 32 °C ( 40 °F to 90 °F )
-40 °C to 50 °C ( -40 °F to 122 °F )
Cooling & Heating: Default: 1.8°C
( 3.2°F )
Dry contact across terminal BI1,
BI2 & UI3 to Scom
14 gauge maximum, 22 gauge
recommended
0.75 lb ( 0.34 kg )
cTUVus: UL 873 (US) and CSA C22.2
No. 24 (Canada)
XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada)
FCC: Compliant to CFR 47, Part 15,
Subpart B (US)
CE : EMC Directive 89/336/EEC
(Europe Union)
C-Tick: AS/NZS CISPR 22 Compliant
(Australia / New Zealand) Supplier
Code Number N10696
FCC: Compliant to: Part 15, Subpart C
CE: R&RTTE Directive 1999/5/EC
(Europe Union)
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT
TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL
INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Please check with your local government for instruction on disposal of this
product