21 | PIR Ready VTR7300 Series-Installation Guide
Unocc HT
Unoccupied heating
setpoint
Default value = 62 °F
Unoccupied heating setpoint range is:
40 to 90 °F ( 4.5 to 32.0 °C )
Unocc CL
Unoccupied cooling
setpoint limit
Default value = 80 °F
Unoccupied cooling setpoint range is:
54 to 100 °F ( 12.0 to 37.5 °C )
Heat max
Maximum heating
setpoint limit
Default value =
90 °F ( 32 °C )
Maximum occupied & unoccupied heating setpoint adjustment.
Heating setpoint range is: 40 to 90 °F ( 4.5 to 32.0 °C )
Cool min
Minimum cooling setpoint
limit
Default value =
54 °F ( 12 °C )
Minimum occupied & unoccupied cooling setpoint adjustment.
Cooling setpoint range is: 54 to 100 °F ( 12.0 to 37.5 °C )
Pband
Proportional band setting
Default is : 3
Adjust the proportional band used by the Terminal Equipment
Controller PI control loop.
Note that the default value of 3.0 °F ( 1.2 °C ) gives
satisfactory operation in most normal installation cases.
The use of a proportional band different than the factory one is
normally warranted in applications where the Terminal
Equipment Controller location is problematic and leads to
unwanted cycling of the unit. A typical example is a wall
mounted unit where the Terminal Equipment Controller is
installed between the return and supply air feeds and is directly
influenced by the supply air stream of the unit.
VALUE
°
F SCALE PBAND
°
C SCALE
PBAND
3
3 F
1.2 C
4
4 F
1.7 C
5
5 F
2.2 C
6
6 F
2.8 C
7
7 F
3.3 C
8
8 F
3.9 C
9
9 F
5.0 C
10
10 F
5.6 C