23 | PIR Ready VT7600 Series-Installation Guide

Pband
Proportional Band setting
Default value 2 = 2.0 °F ( 0.6
°C )

Adjust the proportional band used by the Terminal
Equipment Controller PI control loop.

Note that the default value of 2.0 °F ( 1.1 °C )
gives satisfactory operation in most normal
installation cases. The use of a superior

proportional band different than the factory one is normally
warranted in applications where the Terminal Equipment
Controller location is problematic and leads to unwanted
cycling of the unit. A typical example is a wall mounted
unit where the Terminal Equipment Controller is installed
between the return and supply air feeds and is directly
influenced by the supply air stream of the unit.

Valu

e

F scale

Pband

C scale

Pband

2

2 F

1.1 C

3

3 F

1.7 C

4

4 F

2.2 C

5

5 F

2.8 C

6

6 F

3.3 C

7

7 F

3.9 C

8

8 F

4.4 C


Anticycle
Minimum on/off operation
time for stages
Default value = 2 minutes

Minimum On/Off operation time of cooling & heating
stages.

IMPORTANT, anti-short cycling can be set to 0 minutes for
equipment that posses their own anti cycling timer. Do not
use this value unless the equipment is equipped with such
internal timer. Failure to do so can damage the equipment.
0, 1, 2, 3, 4 & 5 minutes

Anti-short cycling can be set to 0 minutes for equipment
that posses their own anti cycling timer. Do not use that
value unless the equipment is equipped with such internal
timer. Failure to do so can damage the equipment.

Min SH

Minimum supply heat

temperature setpoint

Default value = 64 °F (18 °C)

Sets the minimum supply heat to be maintained by the

controller during occupied periods (Occupied or Temporary

Override).

From 50 °F up to 72 °F (10 °C up to 22 °C)

(increments: 0.5° or 5°)