PROPERTY VALUE RANGE RESTRICTIONS FOR AV OBJECTS
Object name
Object Type
Instance
Minimum
Range Value
Maximum
Range Value
Default Value
User HMI
AV
2
0
11
0
Low Backlight
AV
3
0%
100%
60%
Night Backlight
AV
4
0%
100%
5%
Calibrate Temperature Sensor
AV
7
-
5°F(2.5°C)
0°F (0°C)
COM Address
AV
10
0
254
254
ZigBee PAN ID
AV
11
0
1000
0
ZigBee channel
AV
12
0
25
10
ZigBee Short Address
AV
13
-32768
32767
0
ZigBee IEEE Address
AV
14
0
32767
0
BACnet Stack Poll Rate
AV
16
1
5
4
Discharge Low Limit
AV
20
35°F (1.5°C)
65°F (18°C)
45°F (7°C)
Minimum Fresh Air
AV
21
0 CFM
20000 CFM
0 CFM
Maximum Fresh Air
AV
22
0 CFM
20000 CFM
0 CFM
Minimum CO2
AV
23
0 ppm
2000 ppm
800 ppm
Maximum CO2
AV
24
0 ppm
2000 ppm
1200 ppm
Lua Parameter A
AV
25
-32768
32767
0
Lua Parameter B
AV
26
-32768
32767
0
Lua Parameter C
AV
27
-32768
32767
0
Lua Parameter D
AV
28
-32768
32767
0
Lua Parameter E
AV
29
-32768
32767
0
Lua Parameter F
AV
30
-32768
32767
0
Occupied Heat Setpoint
AV
39
40°F (4.5°C)
90°F (32°C)
72°F (22°C)
Occupied Cool Setpoint
AV
40
54°F (12°C)
100°F (37.5°C)
75°F (24°C)
Standby Heat Setpoint
AV
41
40°F (4.5°C)
90°F (32°C)
69°F (21°C)
Standby Cool Setpoint
AV
42
54°F (12°C)
100°F (37.5°C)
78°F (26°C)
Unoccupied Heat Setpoint
AV
43
40°F (4.5°C)
90°F (32°C)
62°F (16.5°C)
Unoccupied Cooling Setpoint
AV
44
54°F (12°C)
100°F (37.5°C)
80°F (26.5°C)
Default Heating Setpoint
AV
45
65°F (18°C)
80°F (26.5°C)
72°F (22°C)
Standby Temperature Differential
AV
46
10°F (5.5°C)
50°F (28°C)
40°F (22°C)
Main Password
AV
56
0
9999
N/A
User Password
AV
57
0
9999
0