Now to confirm if there is an entry, simply view the property sheet of the BACnet object.
In this view you will confirm an entry at level 16 or any other priority array level.
If the point was overridden by accident and the normal controller operation is required and desired, simply set
the overridden priority array to NULL to resume the controller normal operation under the relinquish default
property value.
Binding to a point using the Fallback
Caution need to be taken when binding objects to specific server logic for central control and applications. The
same cautions that apply to the “set” command apply to the binding of a point using the Niagara “fallback”
proxy extension.
Binding a logic block or function to the “fallback” sets the same behaviour as using the Niagara “set” command.
The local server issues a BACnet write command to the controller
without specifying any