Global command control level device level, Vt8600 series bacnet, Integration manual – Viconics VT8600 Series BACnet Integration Guide User Manual
Page 21: Integration – global commands, All devices, Specific devices
VT8600 Series
BACnet
®
Integration Manual
21
Viconics Technologies Inc.
|
9245 Langelier Blvd.
|
St.-Leonard
|
Quebec
|
Canada
|
H1P 3K9
|
Tel: (514) 321-5660
|
Fax: (514) 321-4150
028-0437-00
www.viconics.com
|
March 2015
©
2
01
5 V
ic
onic
s T
ec
hno
lo
gi
es
Inc
. A
ll r
ig
ht
s r
ese
rv
ed
.
INTEGRATION – GLOBAL COMMANDS
The following figure shows which objects from the controller can be monitored and controlled from the BAS front-end.
Outdoor Temperature (AV101)
System mode (MV16)
Occupancy Command (MV10)
Fan Mode (MV17)
Occupied Heating Setpoint (AV39)
Unoccupied Heating Setpoint (AV43)
Occupied Cooling Setpoint (AV40)
Unoccupied Cooling Setpoint (AV44)
Main Password (AV56)
Room Temperature (AV100)
MS/TP
Network
BAS
Front End
VT8600 Series
controller
Global Command Control Level
Device Level
Figure 1 : Global commands from a BAS front-end to a typical VT86xx series controller
Note: For information about integrating ZigBee wireless sensors with BACnet, refer to the
ZigBee Wireless Sensor Installation Guide.
All Devices
(All controllers)
Outdoor Temperature
Outdoor Temperature and HVAC plant current mode
Specific Devices
(Specific area controllers)
Schedule
Schedule
Outdoor Temperature
Restrict user access to controller
Room temperature for testing and override