Object Type

Read/Write Settings

Object Property

Controller Parameter

Input

AI

Output

AO

Values

AV

Read Only

Read Only

Read Only

Event State
Property 36

Indicates if object has an active event state associated
with it

Read Only

Read Only

Read Only

Object Identifier
Property 75

Unique ID number of an object on a network

Read Only

Read Only

Read Only

Object Name
Property 77

Unique name of an object on a network

Read Only

Read Only

Read Only

Object Type
Property 79

Indicates membership in a particular object type class

Read / Write

Read / Write

Read / Write

Out of Service
Property 81

Indicates whether (TRUE/FALSE) the physical input
object represents is not in service

Read / Write*

Read / Write

Read / Write

Present Value
Property 85

Contains values of all properties specified

N/A

Read Only

Read Only

Priority Array
Property 87

Read-only array of prioritized values

Read Only

Read Only

Read Only

Reliability
Property 103

Indicates if Present_Value is "reliable"

N/A

Read Only

Read / Write

Relinquish Default
Property 104

Default value used for Present_Value when values in
Priority_Array have a NULL value

Read Only

Read Only

Read Only

Status Flags
Property 111

Represents flags that indicate general health of life
safety point object

Read Only

Read Only

Read Only

Units
Property 177

Indicates measurement units of Present_Value

N/A

Read Only

N/A

Hight Limit
Property 1101

Specifies a limit Present_Value must exceed before an
event is generated

N/A

Read Only

N/A

Low Limit
Property 1100

Specifies a limit Present_Value must fall below before
an event is generated

N/A = Not Applicable, property not used for objects of that type
* The Present_Value is only writeable when Out_Of_Service is TRUE.
† Relinquish default is Read Only for AV100+