Read/Write
Object Property
Controller Parameter
Read Only
Event State
Property 36
Indicates object has an active event state associated
with it
Read Only
Object Identifier
Property 75
Unique ID number of a device on a network
Read Only
Object Name
Property 77
Unique name of a device on a network
Read Only
Object Type
Property 79
Indicates membership in a particular object type class
Read / Write
Present Value
Property 85
Contains values of all properties specified
Read Only
Status Flags
Property 111
Represents flags that indicate general health of life
safety point object
CSV OBJECT PROPERTIES
PG OBJECT PROPERTIES
Read/Write
Object Property
Controller Parameter
Read / Write
Description
Property 28
String of printable characters whose content is not
restricted. Contains the LUA program script (max size
= 480 bytes)
Read Only
Description Of Halt
Property 29
Describes the reason why a program has been halted
Text is also displayed in the HMI debug log
Read Only
Instance Of
Property 48
Local name of the application program being
executed by this process
Read Only
Object Identifier
Property 75
Unique ID number of an object on a network
Read Only
Object Name
Property 77
Unique name of an object on a network
Read Only
Object Type
Property 79
Indicates membership in a particular object type class
Read Only
Out Of Service
Property 81
Indicates whether (TRUE/FALSE) the process this
object represents is not in service
Write Only
Program Change
Property 90
Used to request changes to the operating state of the
program. Writing to property affects all 10 PG objects
Read Only
Program State
Property 92
Current logical state of all 10 PG objects executing
application programs
Read Only
Reason For Halt
Property 100
If program halts, this property reflects the reason for
halt for all 10 PG objects
Read Only
Status Flags
Property 111
Represents flags that indicate general health of life
safety point object