beautypg.com

Vt8600 series bacnet, Integration manual, Property value range restrictions for msi objects – Viconics VT8600 Series BACnet Integration Guide User Manual

Page 17: Property value range restrictions for mv objects

background image

VT8600 Series

BACnet

®

Integration Manual

17

Viconics Technologies Inc.

|

9245 Langelier Blvd.

|

St.-Leonard

|

Quebec

|

Canada

|

H1P 3K9

|

Tel: (514) 321-5660

|

Fax: (514) 321-4150

028-0437-00

www.viconics.com

|

[email protected]

March 2015

©

2

01

5 V

ic

onic

s T

ec

hno

lo

gi

es

Inc

. A

ll r

ig

ht

s r

ese

rv

ed

.

PROPERTY VALUE RANGE RESTRICTIONS FOR MSI OBJECTS

Object Name

Object Type

Instance

Index

Text

Default Value

BACnet Status

MSI

1

1

Offline

Offline

2

Online

ZigBee Status

MSI

2

1

Not Detected

N/A

2

Power On

3

No Network

4

Joined

5

Online

Effective Occupancy

MSI

33

1

Occupied

Occupied

2

Unoccupied

3

Override

4

Standby

Wireless Zone 1 Status

MSI

210

1

None

None

2

Closed

3

Opened

4

Motion

5

No Motion

Wireless Zone 1 Battery

MSI

211

1

None

None

2

Normal

3

Low

Wireless Zone 1 Paired

MSI

212

1

No

No

2

Yes

3

Invalid

Wireless Zone 2 Status

MSI

220

1

None

None

2

Closed

3

Opened

4

Motion

5

No Motion

Object Name

Object Type

Instance

Index

Text

Default Value

Wireless Zone 10 Set Function

MV

300

1

None

None

2

Window

3

Door

4

Motion

5

Status

6

Remove

PROPERTY VALUE RANGE RESTRICTIONS FOR MV OBJECTS