Slant/Fin VSPH-180 User Manual

Page 7

background image

V

ICTORY VSPH Models

7

Maximum allowed flue and air intake equivalent length (Feet)

for

Heat-Fab Saf-T vent system (Including EZ Seal)

Boiler Model

Number

Piping

0 - 5,000 Ft.

Elevation

VSPH-60

Flue

40

40

40

Air Intake

40

40

40

VSPH-90

Flue

40

40

35

Air Intake

40

40

40

VSPH-120

Flue

40

35

30

Air Intake

40

40

40

VSPH-150

Flue

35

30

25

Air Intake

40

40

35

VSPH-180

Flue

33

28

23

Air Intake

40

35

30

5,000 - 7,500 Ft.

Elevation

7,500 - 10,000 Ft.

Elevation

Maximum allowed flue and air intake equivalent length (Feet)

for

Z-Flex Z-Vent and Flex-L StaR-34 vent systems

Boiler Model

Number

Piping

0 - 5,000 Ft.

Elevation

VSPH-60

Flue

35

35

35

Air Intake

40

40

40

VSPH-90

Flue

35

35

30

Air Intake

40

40

40

VSPH-120

Flue

35

30

25

Air Intake

40

40

40

VSPH-150

Flue

30

25

20

Air Intake

40

40

35

VSPH-180

Flue

28

23

18

Air Intake

40

35

30

5,000 - 7,500 Ft.

Elevation

7,500 - 10,000 Ft.

Elevation

Maximum allowed flue and air intake equivalent length (Feet)

for

ProTech FasNSeal vent systems

Boiler Model

Number

Piping

0 - 5,000 Ft.

Elevation

VSPH-60

Flue

30

30

30

Air Intake

40

40

40

VSPH-90

Flue

30

30

25

Air Intake

40

40

40

VSPH-120

Flue

30

25

20

Air Intake

40

40

40

VSPH-150

Flue

25

20

15

Air Intake

40

40

35

VSPH-180

Flue

23

18

15

Air Intake

40

35

30

5,000 - 7,500 Ft.

Elevation

7,500 - 10,000 Ft.

Elevation