Slant/Fin VSPH-180 User Manual
Page 7

V
ICTORY VSPH Models
7
Maximum allowed flue and air intake equivalent length (Feet)
for
Heat-Fab Saf-T vent system (Including EZ Seal)
Boiler Model
Number
Piping
0 - 5,000 Ft.
Elevation
VSPH-60
Flue
40
40
40
Air Intake
40
40
40
VSPH-90
Flue
40
40
35
Air Intake
40
40
40
VSPH-120
Flue
40
35
30
Air Intake
40
40
40
VSPH-150
Flue
35
30
25
Air Intake
40
40
35
VSPH-180
Flue
33
28
23
Air Intake
40
35
30
5,000 - 7,500 Ft.
Elevation
7,500 - 10,000 Ft.
Elevation
Maximum allowed flue and air intake equivalent length (Feet)
for
Z-Flex Z-Vent and Flex-L StaR-34 vent systems
Boiler Model
Number
Piping
0 - 5,000 Ft.
Elevation
VSPH-60
Flue
35
35
35
Air Intake
40
40
40
VSPH-90
Flue
35
35
30
Air Intake
40
40
40
VSPH-120
Flue
35
30
25
Air Intake
40
40
40
VSPH-150
Flue
30
25
20
Air Intake
40
40
35
VSPH-180
Flue
28
23
18
Air Intake
40
35
30
5,000 - 7,500 Ft.
Elevation
7,500 - 10,000 Ft.
Elevation
Maximum allowed flue and air intake equivalent length (Feet)
for
ProTech FasNSeal vent systems
Boiler Model
Number
Piping
0 - 5,000 Ft.
Elevation
VSPH-60
Flue
30
30
30
Air Intake
40
40
40
VSPH-90
Flue
30
30
25
Air Intake
40
40
40
VSPH-120
Flue
30
25
20
Air Intake
40
40
40
VSPH-150
Flue
25
20
15
Air Intake
40
40
35
VSPH-180
Flue
23
18
15
Air Intake
40
35
30
5,000 - 7,500 Ft.
Elevation
7,500 - 10,000 Ft.
Elevation