ICTORY VSPH Models

27

D. BURNER SHORT CYCLES

CAUSE

1.

Thermostat heat anticipator set too low.

2.

Excessive pressure drop due to excess venting or air intake

system.

3.

Blockage or restriction in venting or air intake system.

4.

Defective air flow switch (out of adjustment).

REMEDY

1.

Reset anticipator.

2.

System must be corrected.

3.

Check and Repair

4.

Replace. DO NOT adjust.

E. FUMES AND GAS ODORS

CAUSE

1.

Leaks in gas piping or accessories.

2.

Gas leaks in service line or meter connections.

3.

Condensation trap is not full of water.

4.

Venting system is physically damaged.

5.

Over - firing

REMEDY

1.

Locate leaks and repair.

2.

Close service supply valve - shut down boiler and notify

utility

3.

Check and fill with water.

4.

Check carefully and repair. Also, see “Venting System

Regular Inspection”.

5.

Adjust gas input to that shown on boiler rating plate.

IF REPLACEMENT PARTS ARE NEEDED

When parts are needed, refer to boiler model and serial number

shown on the boiler name/rating plate. Refer to publication num-

ber VSPH-10PL replacement parts for part numbers. Whenever

possible refer to the original order by number and date.

Control identification and replacement should not be attempted

by unskilled personnel. Only, simple easily - identified controls

and parts may be obtained locally. All other controls and parts

should be identified by and ordered from Slant/Fin. Relief/Safety

valves must be ASME rated for the pressure and gross output of

the boiler.

For replacement parts, heating contractors should contact their

Slant/Fin boiler distributor.