beautypg.com

Slant/Fin GGT Series User Manual

Modular boiler submittal data, Ggt series—gas-fired/hot water

background image

Modular Boiler Submittal Data

A Caravan modular boiler system consists of two
or more compact cast-iron boilers that offer
significant advantages in terms of installed cost,
efficiency and reliability. Caravan systems are
based on step-firing just enough modules to meet
heating demands. GGT systems are available in
400,000 to multi-million Btuh gross input. For
additional information, see Caravan Engineering
Manual, pub. C-30 and Caravan gas application
guide, pub. CG-10-HWG.

Standard Equipment

One per module unless otherwise noted:
Pre-assembled cast-iron heat exchanger with

built-in air separators and insulated jacket.

Base.
Flue collector.
Gas burners, gas orifices and manifold assembly.
Combination gas valve including manual shut-off

and pressure regulator.

Pilot adjustment and automatic pilot

thermocouple safety.

Hi-limit control.

Ratings

GGT SERIES—Gas-Fired/Hot Water

Module pressure and tempera-

ture gauge (unmounted).

Module pressure relief valve

(ASME) (unmounted). Specify 30,
50 or 100 psi.

Control header (unmounted, one

per system).

Draft hood (unmounted).
Spark ignition system.

Hot water supply and return header

assemblies.

Control panel with automatic lead/lag.
Standing pilot available on:

GG-200EC, GG-250EC, GG-300EC

Vent dampers.
External DHW heat exchanger.

Optional Equipment

* Specify gas by name, "Natural" or

"Propane".

† Net ratings are based on piping and

pick-up allowance of 1.15. Slant/Fin
should be consulted before selecting
a boiler for installation having unusual
piping and/or pick-up requirements.
Ratings must be reduced by 4% at
2,000 ft. elevation and an additional
4% for every additional 1,000 ft.
elevation over 2,000 ft.

‡ Net ratings in square feet based on

emission rate of 150 Btuh/sq. ft.

§ I=B=R gross output.

Modules in excess of 10 should be
piped in parallel in two or more
batteries. For dimension
specifications, refer to Publication
number CG-10-HWG.

Note: Specify pressure relief setting.

Relief valve is available with
30, 50 or 100 psi.

FOR LARGER SIZES, USE MULTIPLES OF THE ABOVE.

®

GGT-400

2

GG-200EC

400

332

1866

280

9.9

14.2

82.0

820

GGT-500

2

GG-250EC

500

402

2333

350

12.0

16.4

80.4

950

GGT-600

2

GG-300EC

600

480

2780

417

14.3

18.4

80.0

1080

GGHT-700

2

GG-350HEC

700

581

3368

505

17.3

20.6

83.0

1230

GGHT-750

2

GG-375HEC

750

608

3520

528

18.1

20.6

81.0

1230

GGHT-800

2

GG-399HEC

798

654

3786

568

19.5

20.6

82.0

1230

GGT-900

3

GG-300C

900

720

4173

626

21.5

27.6

80.0

1590

GGHT-1050

3

GG-350HEC 1050

872

5052

758

26.0

30.9

83.0

1830

GGHT-1125

3

GG-375HEC 1125

912

5286

793

27.2

30.9

81.0

1830

GGHT-1200

3

GG-399HEC 1197

981

5686

853

29.3

30.9

82.0

1830

GGT-1200

4

GG-300C

1200

960

5560

834

28.7

36.8

80.0

2140

GGHT-1400

4

GG350HEC

1400

1162

6736

1010

34.7

41.2

83.0

2440

GGHT-1500

4

GG-375HEC 1500

1216

7046

1057

36.3

41.2

81.0

2440

GGT-1500

5

GG-300EC

1500

1200

6950

1043

35.9

46.0

80.0

2675

GGHT-1600

4

GG-399HEC 1596

1308

7580

1137

39.0

41.2

82.0

2440

GGHT-1750

5

GG-350HEC 1750

1453

8420

1263

43.4

51.5

83.0

3050

GGHT-1875

5

GG-375HEC 1875

1520

8806

1321

45.4

51.5

81.0

3050

GGHT-2000

5

GG-399HEC 1995

1635

9473

1421

48.8

51.5

82.0

3050

GGHT-2100

6

GG-350HEC 2100

1743

10104

1516

52.0

61.8

83.0

3660

GGHT-2250

6

GG-375HEC 2250

1824

10573

1586

54.4

61.8

81.0

3660

GGHT-2400

6

GG-399HEC 2394

1962

11373

1706

58.6

61.8

82.0

3660

GGHT-2450

7

GG-350HEC 2450

2034

11788

1768

60.7

72.1

83.0

4270

GGHT-2625

7

GG-375HEC 2625

2128

12333

1850

63.5

72.1

81.0

4270

GGHT-2800

7

GG-399HEC 2793

2289

13266

1990

68.3

72.1

82.0

4270

GGHT-2800

8

GG-350HEC 2800

2324

13472

2021

69.4

82.4

83.0

4880

GGHT-3000

8

GG-375HEC 3000

2432

14093

2114

72.6

82.4

81.0

4880

GGHT-3150

9

GG-350HEC 3150

2615

15157

2273

78.1

92.7

83.0

5490

GGHT-3200

8

GG-399HEC 3192

2616

15160

2274

78.1

82.4

82.0

4880

GGHT-3375

9

GG-375HEC 3375

2736

15860

2379

81.7

92.7

81.0

5490

GGHT-3500

10

GG-350HEC 3500

2905

16841

2526

86.8

103.0

83.0

6100

GGHT-3600

10

GG-399HEC 3591

2943

17060

2559

87.9

92.7

82.0

5490

GGHT-3750

10

GG-375HEC 3750

3040

17620

2643

90.8

103.0

81.0

6100

GGHT-4000

10

GG-399HEC 3990

3270

18953

2843

97.6

103.0

82.0

6100

Gas Caravan ratings and dimensions/hot water models — GGT Series

Model No. *

Consists of

I=B=R Ratings

(MBH)

Input

Gross

Output§

Ship

Wt.

No. of

Htg.

Mod.§

EDR

Water‡

(Sq. Ft.)

Boiler

Horse-

power

Water

Content

(gal.)

A.G.A.

Combust.

Efficiency

I=B-R

Net

Output†

(MBH)

Module

Model

Number