Step 5 – program the communicator – SilentKnight IPGSM-4G User Manual
Page 8
IPGSM-4G Commercial Fire Communicator – Installation and Setup Guide
– 6 –
STEP 5 – Program the Communicator
You must use the 7720P Programming tool to program the IPGSM-4G.
When using the 7720P Programming tool, the values given below are for most installations. Press the [#] key to ac-
cept the displayed default value (xxx) or enter the new value and press the [#] key for the next prompt. Use the
[Space] key to scroll through a list of options.
1.
Connect the 7720P. (You can use the [Shift + A] key to check the software revision.)
2.
7720P PROGRAMMER
Press [#].
3.
Strt Prog Mode? Y/N
Press [Shift] then [Y], then [#].
4.
Program Device? Y/N
Press [Shift] then [Y], then [#].
5.
Com Path Choice (IP & GSM)
Press [Space] to scroll choices; IP&GSM, IP, or GSM. Press [#] to select.
The IP Fault Time, and the GSM Fault Time that correspond to the choices are:
Choice
Supervision Interval
IP Fault Time GSM Fault Time
2010 IP & GSM
24 hours
1 hour
1 hour
2013 IP
1 hour
1 hour
- - -
2013 GSM
1 hour
- - -
1 hour
2013 IP & GSM
6 hours
1 hour
1 hour
2010 IP
5 minutes
5 minutes
- - -
2010 GSM
5 minutes
- - -
5 minutes
6.
Primary City ID (??)
Enter number 01-99, then press [#].
7.
Primary CS ID (??)
Enter number 01-FE, then press [#].
8.
Primary Sub ID (????)
Enter number 0001-9999, then press [#].
Note: If a Com Path Choice of IP & GSM or IP was selected, prompt 9 will appear.
9.
Use DHCP? Y/N (Y)
If your router is configured for DHCP, press [Shift] then [Y], then press [#].
Note: If DHCP is not selected (your router is set for a static IP), prompts 10 through 13 will appear. Use
the [Space] key to advance to the next address part.
10. NIC IP Address:
255.255.255.255
Enter choice, then press [#]. Follow the prompts.
11. Subnet Mask:
255.255.255.255
Enter choice, then press [#]. Follow the prompts.
12. Gateway IP Address:
255.255.255.255
Enter choice, then press [#]. Follow the prompts.
13. DNS Serv IP Addr:
255.255.255.255
Enter choice, then press [#]. Follow the prompts.
14. Review? Y/N
Enter choice, then press [#]. Follow the prompts.
15. Create Password? Y/N
Enter choice, then press [#]. Follow the prompts.
16. Exit Prog Mode? Y/N
Press [Shift] then [Y], then press [#]. DONE.
Notes:
•
If an error in programming occurs, set the factory defaults (see next topic) and reprogram.
Note: The 2013 choices
have been evaluated to
meet NFPA 2013 supervision
requirements and are sub-
ject to approval by the local
authority having jurisdiction.
(See back cover.)