Ipgsm-4g trouble detection information, Ipgsm-4g specifications – SilentKnight IPGSM-4G User Manual
Page 14
IPGSM-4G Commercial Fire Communicator – Installation and Setup Guide
– 12 –
IPGSM-4G Trouble Detection Information
Telco 1 is used for the Fire Panel to output contact ID messages to the IPGSM-4G, and Telco 2 is used by the IPGSM-
4G to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use Telco 2 to report events if
there are no faults in the Communicator.
Fault Condition
Indication to Fire Panel
PowerBoost1 fault
Telco 2 is cut.
Communicator fault
•
Failure of the communications path when
IP only or GSM only is programmed as a
communications path.
Telco 2 is cut.
•
Failure of both communications paths
when IP&GSM is programmed as a com-
munications path.
Telco 1 and 2 are cut.
Dialer Capture Module buffer is full.
Hang up. (Panel will retry, giving the buffer a chance
to empty.)
IPGSM-4G Specifications
ITEM
SPECIFICATION
Cabinet Dimensions:
Width 12 3/4 inches, Height 14 7/8 inches, Depth 3 inches
Transformer: N8167
Primary – 120VAC, 60Hz, Secondary – 18VAC, 50VA
Battery:
12V, 7Ah sealed lead acid type (not supplied)
Use a Honeywell 712BNP, Yuasa NP7-12 or equivalent.
Battery Charging Current:
maximum 1A
Battery Discharge Current: standby 230mA, active 950mA
Environment:
Operating temperature: –20º to +55ºC, for UL installations 0ºC to
+49ºC
Storage temperature: –40º to +70ºC
Humidity: 0 to 95% relative humidity, non-condensing, for UL instal-
lations 0% to 93%
Altitude: to 10,000 ft. operating, to 40,000 ft. storage
Supervision:
The Radio (communicator), battery, and AC power, conditions are
monitored by the cabinet indicator LEDs:
RADIO TROUBLE lights when any of these conditions exist.
•
Both IP and GSM communication paths are lost.
•
Communicator radio is not registered.
•
Old Alarm Time has been exceeded. (Message has not been de-
livered within the fixed 10 minute window.)
LOW BATTERY lights when the battery voltage is less than 11.5VDC.