beautypg.com

Dialer capture module information, Led display information – SilentKnight IPGSM-4G User Manual

Page 10

background image

IPGSM-4G Commercial Fire Communicator – Installation and Setup Guide

– 8 –

Dialer Capture Module Information

LED Indicator

STATUS

RED – Steady ON

Messages exist in buffer.

RED – Flashing

No messages to be sent. Waiting for messages.

GREEN – Steady ON

Normal Indication.

GREEN – Blinks every 2 sec.

PowerBoost1 communication problem.

GREEN – Blinks twice every sec.

Connection with the Communicator is lost.

GREEN – Blinks 10 times every sec.

PowerBoost1 and Communicator connections are lost.


LED Display Information

Status

LED Indicator

RADIO TROUBLE

Yellow – ON when radio trouble is present.

Both IP and GSM communication paths are lost.

Communicator radio is not registered.

Old Alarm Time has been exceeded. (Message has not been

delivered within the fixed 10 minute window.)

Buzzer – Upon loss of AC power, this will beep once every 10

seconds.

LOW BATTERY

Yellow – ON when battery is low (<11.5VDC).

Yellow – (not used)

AC LOSS

Yellow – ON when no AC is present (< 90VAC).

AC ON

Green – ON when AC is present.

Note: If a wire pulled out of the LED Board Connector

refer to the diagram on right and reinsert wire, ensuring

the connector pin is locked in.




Note: Telco ports 1 (primary dialer)

and 2 (secondary dialer) may be used

instead of the terminal board.
Whichever connection method is used,

both Telco paths must be connected to

the Fire Panel.

NC
NC

LED Board

Connector

Wires

Violet

Black

White

Red
Brown

Yellow

Gray