Rating plate and serial no. ( model vr ), Important, Example – Reznor VR Parts Manuals User Manual
Page 2: Rating plate key, Codes: serial no. decoding, Reznor

Form P-RIH/VR, PN 272513, Page 2
Size Conversion Label - Model VR - When servicing a heater with a rating plate reading Model VR75, VR125, or
VR175,
always look for a Size Conversion label.
• Rating Plate reads Model VR75 AND Size Conversion Label reads VR100 - Service heater as a Model VR100.
• Rating Plate reads Model VR125 AND Size Conversion Label reads VR150 - Service heater as a Model VR150.
• Rating Plate reads Model VR175 AND Size Conversion Label reads VR200 - Service heater as a Model VR200.
Year
Jan
Feb
Mar
Apr
May
June
July
Aug
Sept
Oct
Nov
Dec
2002
BBA
BBB
BBC
BBD
BBE
BBF
BBG
BBH
BBI
BBJ
BBK
BBL
2003
BCA
BCB
BCC
BCD
BCE
BCF
BCG
BCH
BCI
BCJ
BCK
BCL
2004
BDA
BDB`
BDC
BDD
BDE
BDF
BDG
BDH
BDI
BDJ
BDK
BDL
2005
BEA
BEB
BEC
BED
BEE
BEF
BEG
BEH
BEI
BEJ
BEK
BEL
2006
BFA
BFB
BFC
BFD
BFE
BFF
BFG
BFH
BFI
BFJ
BFK
BFL
2007
BGA
BGB
BGC
BGD
BGE
BGF
BGG
BGH
BGI
BGJ
BGK
BGL
2008
BHA
BHB
BHC
BHD
BHE
BHF
BHG
BHH
BHI
BHJ
BHK
BHL
2009
BIA
BIB
BIC
BID
BIE
BIF
BIG
BIH
BII
BIJ
BIK
BIL
2010
BJA
BJB
BJC
BJD
BJE
BJF
BJG
BJH
BJI
BJJ
BJK
BJL
2011
BKA
BKB
BKC
BKD
BKE
BKF
BKG
BKH
BKI
BKJ
BKK
BKL
2012
BLA
BLB
BLC
BLD
BLE
BLF
BLG
BLH
BLI
BLJ
BLK
BLL
2013
BMA
BMB
BMC
BMD
BME
BMF
BMG
BMH
BMI
BMJ
BMK
BML
2014
BNA
BNB
BNC
BND
BNE
BNF
BNG
BNH
BNI
BNJ
BNK
BNL
2015
BOA
BOB
BOC
BOD
BOE
BOF
BOG
BOH
BOI
BOJ
BOK
BOL
IMPORTANT
This appliance has been converted at the time of installation to a model
Cet appareil a ete converti au moment de l’installation en un modele _____(100, 150, or 200) _____
by
with kit no.
per ________(name of service person or agency)_________
avec la kit n
o
__(Kit P/N)___
which accepts the responsibility that this conversion has been properly made.
ce qui accepte la responsabilite que cette conversion a ete correctement faite.
Orifice Size
Dimension de l’orifice
__(New Orifice Size)__Drill Foret
Normal input
Entrée Normale
__(100,000; 150,000; or 200,000)_BTU/HR
Minimum permissible gas supply pressure for purpose of input adjustment _(*)_in. w.c.
Pres. D’alim. Min. acceptable de gaz pour des fin de reglace de l’entrée
__(*)__ PO/COL D’eau
Rating Plate and
Serial No. (Model VR)
Rating Plate Key:
A = Model
B = ANSI Certification
C = CSA Certification
D = Mfg Date (month & year)
E = Supply Voltage
F = Type of Fuel (natural gas or
propane)
G = Burner Orifice Drill Size
H = Input (BTUH)
I = Manifold Pressure (“ w.c.)
J = Minimum Gas Supply
(inches w.c.)
K = Clearances to
Combustibles - Burner End
L = Clearance to Combustibles
- Heat Exchanger Bend
M = Clearance to Combustibles
- Below
N = Clearance to Combustibles
- Front/Rear, 0-30°
Reflector
O = Clearance to Combustibles
- Front/Rear, 31-45°
Reflector
P = Clearance to Combustibles
- Front/Rear, 0-30°
Reflector with Side Shield
CODES:
Serial No. Decoding
Example:
BJK 80 6A N 12345
1
2
3
4
5
First Element of the
Serial Number - Date of
Manufacture (Model VR)
REZNOR
®
MERCER, PA. USA 16137
MADE IN MEXICO
NRTL
INFRARED RADIANT TUBE HEATER
FOR INDUSTRIAL/COMMERCIAL USE ONLY
FOR INDOOR INSTALLATION ONLY. NOT FOR USE IN RESIDENTIAL
DWELLINGS CERTIFIED UNDER ANSI Z83.20b - [ B ] CSA 2.34b - [ C ]
LOW INTENSITY INFRARED HEATER
MODEL
[ A ]
SERIAL #
[ C ]
[ E ] VOLTS [ E ] PH [ E ] HZ MAXIMUM TOTAL INPUT [ E ] AMPS
TYPE OF GAS
[ F ]
FOR USE AT 0-2000 FEET, 0-610 METERS OF ALTITUDE
ORIFICE SIZE
[ G ] DRILL
NORMAL INPUT
[ H ] BTU/HR
NORMAL MANIFOLD PRESSURE [ I ] IN. W.C.
MIN PERMISSIBLE AS SUPPLY PRESSURE FOR
PURPOSE OF INPUT ADJUSTMENT
[ J ] IN. W.C.
CLEARANCE TO COMBUSTIBLE CONSTRUCTION: TOP - 12”*; FLUE
CONNECTION - 6”; BURNER END [ K ]; EXHAUST END - 24”; HEAT
EXCHANGER BEND (U OR L) [ L ]
*18” IF UNVENTED
REFLECTOR
MAX MOUNTING
ANGLE
BELOW
(FRONT/
REAR)
STANDARD REFLECTOR
0 TO 30 DEG
[ M ]
[ N ]
STANDARD REFLECTOR
31 TO 45 DEG
[ M ]
[ O ]
STANDARD REFLECTOR W/SIDE
SHIELDS (ONE SIDE ONLY)
0 TO 30 DEG
[ M ]
[ P ]
THIS UNIT CAN BE INSTALLED IN VARIABLE CONFIGURATIONS AS
SPECIFIED IN THE MANUFACTURER’S FORM T-VR-CNFG.
FOR STRUCTURES LISTED BELOW, USE APPLICABLE STANDARDS.
INSTALLATION OF THIS UNIT IN AIRCRAFT HANGARS IN CANADA
MUST BE IN ACCORDANCE WITH THE REQUIREMENTS OF THE
ENFORCING AUTHORITIES.
IN PUBLIC GARAGES, IN ACCORDANCE WITH THE CAN/CGA-B149 (.1
OR .2) CODES IN CANADA.
AIRCRAFT HANGARS USE STANDARD ANSI/NFPA 409 IN THE USA
PARKING STRUCTURES USE STANDARD ANSI/NFPA 88A IN THE USA
REPAIR GARAGES USE STANDARD ANSI/NFPA 88B IN THE USA
FOR USE WITH TYPE L VENT
FOR INDOOR INSTALLATION ONLY
THIS UNIT IS FOR USE WITH NATURAL GAS AND PROPANE
A CONVERSION KIT AS SUPPLIED BY THE MANUFACTURER SHALL
BE USED TO CONVERT THE HEATER TO THE ALTERNATE FUEL.
REZNOR
®
MERCER, PA. USA 16137
FABRIQUÉ AU MEXIQUE
NRTL
INFRARED RADIANT TUBE HEATER
POUR USAGE INDUSTRIEL/COMMERCIAL SEUL
INSTALLATION ÀĹINTÉRIEUR SEULEMENT. NE PAS INSTALLER DANS
UN LOGEMENT. CERTIFIED UNDER ANSI Z83.20b - [ B ] CSA 2.34b - [ C
] LOW INTENSITY INFRARED HEATER
MODELE
[ A ]
#DE SÉRIE
[ D ]
[ E ] VOLTS [ E ] PH [ E ] HZ CONSOMMATION TOTALE MAX. DE [ E ]
AMPS
TYPE DE GAZ
[ F ]
PRÉVU POUR 0-2000 PIEDS, 0-610 MÉTRES D’ALTITUDE
DIMENSION DE L’ORIFICE
[ G ] FORET
ENTRÉE NORMALE
[ H ] BTU/HEURE
PRESSION NORMALE DE
LA TUB
[ I ] PO/COL D’EAU
PRES. D’ALIM. MI. ACCEPTABLE DE GAZ PÓUR
DES FIN DE RÉGLACE DE L’ENTREE
[ J ] PO/COL
D’EAU
DÉGAGEMENT ENTREE LES CONSTRUCTIONS COMBUSTIBLES: EN
HAUT - *12 PO, RACCORD DE TUYAUX - 6 PO, CÓTÉ BRULEUR - [ K ];
CÓTÉ EVACUATION - 24 PO, COUDE D’ÉCHANGEUR (U OR L) [ L ]
*18 PO SI NON VENTILÉ
RÉFLECTEUR
ANGLE DE MONTAGE
MAX.
DESSOUS
(AVANT/
ARRIÉRE)
RÉFLECTEUR STANDARD
0 Â 30 DEG
[ M ]
[ N ]
RÉFLECTEUR STANDARD
31 Â 45 DEG
[ M ]
[ O ]
RÉFLECTEUR STANDARD
AVEC CÓTÉ ÉCRANS (UN CÓTÉ
SEULEMENT)
0 Â 30 DEG
[ M ]
[ P ]
CET APPAREIL PEUT ÊTRE INSTALLÉ SELON DES CONFIGURATION
VARIABLES COMME IL EST STIPULÉ DANS LE FORMULAIRE T-VR-
CNFG DU FABRICANT
L’INSTALLATION DE UNITE DANS CES GARAGES D’AVIONS DOIT SE
CONFORMER AUX CONDITIONS DES AUTHORITÉS CHARGÉES DE
FAIRE.
APPLIQUER LA LOI. L’INSTALLATION DANS DES GARAGES PUBLICS
DOIT SE CONFORMER AU CODE CAN/CGA-B149 (.1 OU.2).
S’UTILISE AVEC UN ÊVENT DE TYPE L.
FOR INDOOR INSTALLATION ONLY
CET APPAREIL POUR UTILISATION AVEC LE GAZ NATURAL ET LE
PROPANE.
UNE TROUSSE DE CONVERSION FOURNIE PAR LE FABRICANT UNE
TROUSSE DE CONVERSION FOURNIE PAR LE FABRICANT
Example of a Size
Conversion Label
* Minimum supply pressure
is 5” w.c. for natural gas for
Sizes 50-150; 6” w.c. for
natural gas for Sizes 175-
200; or 10” w.c. for propane
gas for all sizes.
1 = Date of manufacture (see chart below)
2 = Type of ignition
3 = Type of valve
4 = Type of gas (N= Natural; L= Propane)
5 = Consecutive number (for identification purposes only)