Airflow data, Table 13. airflow settings for cooling mode, Table 12. nominal heating airflow rates – Reznor R6GI Unit Installation Manual User Manual
Page 27: Temperature rises (° f), For heating mode, 5, 6, 7, & 8 on the blower control board, Lists the recommended airflow values (cfm) and, Table 13, And the system is properly, 1, 2, 3, & 4 on the blower control board
27
Table 14
Table 13
Table 12
Airflow Data
Table 14.
Airflow Settings (CFM) & Rise (° F) for Heating Mode
MODEL NUMBER
HEATING INPUT
(BTUH)
HEATING OUTPUT
(BTUH)
HEATING
RANGE
HEATING RISE
RANGE (°F)
BLOWER
SIZE
MOTOR
(HP)
E24K080X
80,000
64,800
1025 - 1375
35-65
11 X 8
1/2
52,000
42,100
800 - 1050
E36K100X
100,000
81,000
1150 - 1500
40-70
11 X 8
1/2
65,000
52,650
875 - 1200
E48K120X
120,000
97,200
1550 - 2000
40-70
11 X 10
1
78,000
63,180
1200 - 1575
E60K120X
120,000
97,200
1550 - 2000
40-70
11 X 10
1
78,000
63,180
1200 - 1575
NOTE: CFM and Rise are independent of ESP in a variable speed blower.
Table 13.
Airflow Settings for Cooling Mode
2 TON CFM SETTINGS
3 TON CFM SETTINGS
4 TON CFM SETTINGS
5 TON CFM SETTINGS
COOLING
BLOWER
SELECTOR
SETTING
RECOMMENDED
AIRFLOW
(HIGH CFM)
COOLING
BLOWER
SELECTOR
SETTING
RECOMMENDED
AIRFLOW
(HIGH CFM)
COOLING
BLOWER
SELECTOR
SETTING
RECOMMENDED
AIRFLOW
(HIGH CFM)
COOLING
BLOWER
SELECTOR
SETTING
RECOMMENDED
AIRFLOW
(HIGH CFM)
(1) 5
6
7
8
(1) 5
6
7
8
(1) 5
6
7
8
(1) 5
6
7
8
0
0
0
0
0
650
1
0
0
0
0
900
0
0
0
0
0
1375
1
0
0
0
0
1500
0
0
0
0
1
680
1
0
0
0
1
935
0
0
0
0
1
4
TON
1400
1
0
0
0
1
1540
0
0
0
1
0
710
1
0
0
1
0
970
0
0
0
1
0
1425
1
0
0
1
0
5
TON
1580
0
0
0
1
1
2
TON
740
1
0
0
1
1
1005
0
0
0
1
1
1450
1
0
0
1
1
1620
0
0
1
0
0
770
1
0
1
0
0
1040
0
0
1
0
0
1475
1
0
1
0
0
1660
0
0
1
0
1
800
1
0
1
0
1
1075
0
0
1
0
1
1500
1
0
1
0
1
1700
0
0
1
1
0
830
1
0
1
1
0
3
TON
1110
0
0
1
1
0
1525
1
0
1
1
0
1740
0
0
1
1
1
860
1
0
1
1
1
1145
0
0
1
1
1
1550
1
0
1
1
1
1780
0
1
0
0
0
890
1
1
0
0
0
1180
0
1
0
0
0
1575
1
1
0
0
0
1820
0
1
0
0
1
920
1
1
0
0
1
1215
0
1
0
0
1
1600
1
1
0
0
1
1860
0
1
0
1
0
950
1
1
0
1
0
1250
0
1
0
1
0
1625
1
1
0
1
0
1900
0
1
0
1
1
980
1
1
0
1
1
1285
0
1
0
1
1
1650
1
1
0
1
1
1940
0
1
1
0
0
1010
1
1
1
0
0
1320
0
1
1
0
0
1675
1
1
1
0
0
1980
0
1
1
0
1
1040
1
1
1
0
1
1355
0
1
1
0
1
1700
1
1
1
0
1
2020
0
1
1
1
0
1070
1
1
1
1
0
1390
0
1
1
1
0
1750
1
1
1
1
0
2060
0
1
1
1
1
1100
1
1
1
1
1
1425
0
1
1
1
1
1800
1
1
1
1
1
2100
NOTES: Dip switch positions - 0 = OFF 1 = ON
1. Switch (1) selects blower program in conjunction with motor horsepower. 0 = 2 or 4 Ton, 1 = 3 or 5 Ton.
2. Recommended CFM’s (factory settings) are highlighted in bold.
Table 12. Nominal Heating Airflow Rates & Temperature Rises (° F)
HEATING
BLOWER
SELECTOR
SETTING
2 TON CFM SETTINGS
HEATING
BLOWER
SELECTOR
SETTING
3 TON CFM SETTINGS
HEATING
BLOWER
SELECTOR
SETTING
4 TON CFM SETTINGS
HEATING
BLOWER
SELECTOR
SETTING
5 TON CFM SETTINGS
LOW
HEAT
HIGH
HEAT
LOW
HEAT
HIGH
HEAT
LOW
HEAT
HIGH
HEAT
LOW
HEAT
HIGH
HEAT
64,800
80,000
81,000
100,000
97,200
120,000
97,200
120,000
(1) 2
3
4 CFM RISE CFM RISE (1) 2
3
4 CFM RISE CFM RISE (1) 2
3
4 CFM RISE CFM RISE (1) 2
3
4 CFM RISE CFM RISE
0 0
0
0 800
50 1025 59
1 0
0
0 875
56 1150 66
0 0
0
0 1200 54 1550 57
1 0
0
0 1200
54
1550 57
0 0
0
1 850
48 1075 57
1 0
0
1 925
53 1200 63
0
0
0
1 1250
50
1650
54
1
0
0
1 1250
50
1650 54
0 0
1
0 875
46 1125 55
1 0
1
0 975
50 1300 58
0 0
1
0 1300 47 1750 52
1 0
1
0 1300 47 1750 52
0 0
1
1 925
44 1175 53
1 0
1
1 1000 48 1350 56
0 0
1
1 1375 44 1800 50
1 0
1
1 1375 44 1800 50
0 1
0
0 950
42 1225 51
1 1
0
0 1050 46 1375 55
0
1
0
0 1450
42
1850
48
1
1
0
0 1450
42
1850 48
0 1
0
1 1000 40 1275 49
1 1
0
1 1100 44 1400 54
0 1
0
1 1475 40 1900 47
1
1
0
1 1475
40
1900 47
0 1
1
0 1025 39 1325 47
1 1
1
0 1150 42 1450 52
0 1
1
0 1525 39 1950 46
1 1
1
0 1525 39 1950 46
0 1
1
1 1050 38 1375 45
1 1
1
1 1200 41 1500 51
0
1
1
1 1575
38
2000
45
1
1
1
1 1575
38
2000 45
1. Switch (1) selects blower program in conjunction with motor horsepower. 0 = 2 or 4 Ton, 1 = 3 or 5 Ton.
2. Recommended CFM’s (Factory settings) and temperature rises are highlighted in bold. Use of any other setting may result in nuisance trips.
3. Temperature rises in tables are approximate. Actual temperature rises may vary.