Warning – Reznor Q6SD (3ph) Unit Installation Manual User Manual
Page 13

13
2. Immediately lower the set point temperature of the
thermostat to its original setting and verify that the 
indoor blower is energized.
3. After approximately 5 minutes, verify the compressor
and fan energize and the temperature of the discharge 
air is cooler than the room temperature. 
System Cooling
1. Set the thermostat’s system mode to COOL and the 
fan mode to AUTO. Gradually lower the thermostat 
temperature setpoint below room temperature and 
verify the outdoor unit and indoor blower energize.
2. Feel the air being circulated by the indoor blower
and verify that it is cooler than ambient temperature. 
Listen for any unusual noises. If unusual sounds 
occur, determine the source of the noise and correct 
as necessary.
3. Allow the cooling system to operate for several minutes
and then set the temperature selector above room 
temperature. Verify the fan and compressor cycle off 
with the thermostat. NOTE: The blower should also 
stop unless fan mode is set to ON.
System Heating
If the unit has been equipped with optional electric heater 
kits, set the thermostat's system mode to HEAT and the 
fan mode to AUTO. Verify the compressor and outdoor 
fan are not energized but that the blower and heaters are. 
Feel the air being circulated by the indoor blower and verify 
that it is warmer than ambient temperature. Listen for any 
unusual noises. If unusual sounds occur, determine the 
source of the noise and correct as necessary.
Refrigerant Charging
WARNING:
Q6SD Heat Pumps are shipped fully charged 
with R-410A refrigerant and ready for installation. 
When a system is installed according to these 
instructions, no refrigerant charging is required. 
If repairs make it necessary for evacuation and 
charging, it should only be done by qualifi ed, 
trained personnel thoroughly familiar with this 
equipment. Some local codes require licensed 
installation/service personnel to service this type 
of equipment. Under no circumstances should 
the owner attempt to install and/or service this 
equipment. Failure to comply with this warning 
could result in property damage, personal injury, 
or death.
The system refrigerant charge can be checked and 
adjusted through the service ports provided at the front 
panel. Use only gauge lines which have a Schrader 
depression device present to actuate the valve.
Table 3. Thermostat Wire Gauge
Thermostat
Wire Gauge
Recommended T-Stat Wire Length
(Unit to T-Stat)
2-Wire
(Heating)
5-Wire
(Heating/Cooling)
24
55
25
22
90
45
20
140
70
18
225
110
START UP & ADJUSTMENTS
Pre-Start Check List
 Verify the unit is level and allows condensate to drain.
 Verify the outdoor coil and top of the unit are free from
obstructions and debris, and all equipment access/
control panels are in place.
 Verify that the duct work is sealed to prevent air leakage.
 Verify that the line voltage power leads are securely
connected and the unit is properly grounded.
 Verify that the low voltage wires are securely connected
to the correct leads on the low voltage terminal strip.
 Verify that the outdoor fan turns freely.
 Verify that the power supply branch circuit overcurrent
protection is sized properly.
 Verify that the thermostat is wired correctly. The
thermostat system mode should be set to OFF and 
the thermostat fan mode should be set to AUTO.
Start-Up Procedure
Close all electrical disconnects to energize the system.
WARNING:
If the unit is equipped with a crankcase heater, 
allow 24 hours prior to continuing the start up 
procedures to allow for heating of the refrigerant 
compressor crankcase. Failure to comply may 
result in damage and could cause premature 
failure of the system. This warning should be 
followed at initial start up and any time the power 
has been removed for 12 hours or longer.
Air Circulation
Leave the thermostat system mode on OFF, and set the 
fan mode to ON. Blower should run continuously. Check 
the air delivery at the supply registers and adjust register 
openings for balanced air distribution. Examine ductwork 
for leaks or obstruction if insuffi cient air is detected. Set 
the thermostat fan mode to AUTO. The blower should 
stop running.
Short Cycle Protection
1. With the system operating in cooling mode, note the 
temperature setting of the thermostat and gradually 
raise the set-point temperature until the unit de-
energizes.
